SIEMENS
4/63
Siemens D 35 · 2017
■
Technical specifications
(continued)
4
SINAMICS G120P built-in and wall-mounted units
PM330 Power Modules, 160 kW to 630 kW
PM330 Power Modules
Line voltage 380 ... 480 V 3 AC
PM330 Power Modules
6SL3310-1PE38-4AA0
6SL3310-1PE38-8AA0
6SL3310-1PE41-0AA0
Rated power
1)
• Based on the base-load current
I
L
-
At 400 V/50 Hz
kW
450
500
560
-
At 460 V/60 Hz
hp
500
600
700
• Based on the base-load current
I
H
-
At 400 V/50 Hz
kW
355
400
450
-
At 460 V/60 Hz
hp
450
500
500
Output current
at 50 Hz 3 AC
• Rated current
I
rated
(400 V ±10 %)
A
840
910
1021
• Rated current
I
rated
(480 V ±10 %)
A
677
739
847
• Base-load current
I
L
(400 V ±10 %)
2)
A
820
890
1000
• Base-load current
I
L
(480 V ±10 %)
2)
A
663
724
830
• Base-load current
I
H
(400 V ±10 %)
3)
A
672
728
786
• Base-load current
I
H
(480 V ±10 %)
3)
A
542
591
652
• Max. output current
I
max
A
1107
1202
1350
Rated pulse frequency
kHz
2
2
2
Input current
4)
• Rated current
I
rated
(400 V ±10 %)
A
870
945
1061
• Rated current
I
rated
(480 V ±10 %)
A
702
767
880
• Base-load current
I
L
(400 V ±10 %)
2)
A
850
924
1038
• Base-load current
I
L
(480 V ±10 %)
2)
A
687
751
862
• Base-load current
I
H
(400 V ±10 %)
3)
A
696
756
816
• Base-load current
I
H
(480 V ±10 %)
3)
A
561
614
677
• Max. input current
A
1147
1248
1402
Short-circuit current rating
according to IEC
in conjunction with the specified fuses
kA
100
100
100
Rated short-circuit current SCCR
(Short-Circuit Current Rating)
in accordance with UL 61800-5-1
(up to 600 V)
in conjunction with the specified fuses
kA
100
100
100
Minimum short-circuit current
5)
• For 3NE1 fuses
A
10400
14000
16000
• For 3NA3 fuses
A
40000
40000
52000
• For 3NB3 fuses
A
8600
17000
18000
Efficiency
η
At rated current
I
rated
(400 V/45 °C (113 °F))
%
98
98
98
Power loss
At rated current
I
rated
(400 V/45 °C (113 °F))
kW
10.418
10.885
12.495
Coolant requirements
m
3
/s (ft
3
/s)
0.45 (15.9)
0.45 (15.9)
0.45 (15.9)
Coolant
Air
Air
Air
Sound pressure level
L
pA
(1 m)
dB
74
74
74
Power requirement 24 V DC supply
A
0.5
0.5
0.5
1)
Rated power of a typical 4-pole standard induction motor based on the
base-load current
I
L
or
I
H
at 400 V 3 AC/50 Hz (kW) or 460 V 3 AC/60 Hz
(hp).
2)
The base-load current
I
L
is based on the duty cycle for low overload (LO).
3)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
4)
The input current depends on the motor load and line impedance and
applies for a line impedance corresponding to
u
K
= 1 %. The rated input
currents apply for a load at rated power (based on
I
rated
) – these current
values are specified on the rating plate.
5)
10 ms value from current-time characteristic for reliable tripping of installed
protection devices. If the minimum short-circuit current is not reached, the
tripping time of the fuses is increased, which can lead to damage.
© Siemens AG 2017