SIEMENS
4/61
Siemens D 35 · 2017
■
Technical specifications
(continued)
4
SINAMICS G120P built-in and wall-mounted units
PM330 Power Modules, 160 kW to 630 kW
PM330 Power Modules
PM330 Power Modules
Line voltage 380 ... 480 V 3 AC
PM330 Power Modules
6SL3310-
1PE33-0AA0
6SL3310-
1PE33-7AA0
6SL3310-
1PE34-6AA0
6SL3310-
1PE35-8AA0
6SL3310-
1PE36-6AA0
6SL3310-
1PE37-4AA0
Rated power
1)
• Based on the base-load current
I
L
-
At 400 V/50 Hz
kW
160
200
250
315
355
400
-
At 460 V/60 Hz
hp
200
250
300
400
450
500
• Based on the base-load current
I
H
-
At 400 V/50 Hz
kW
132
160
200
250
250
315
-
At 460 V/60 Hz
hp
150
200
200
300
300
350
Output current
at 50 Hz 3 AC
• Rated current
I
rated
(400 V ±10 %)
A
300
370
460
585
655
735
• Rated current
I
rated
(480 V ±10 %)
A
245
308
369
487
526
602
• Base-load current
I
L
(400 V ±10 %)
2)
A
290
360
450
570
640
720
• Base-load current
I
L
(480 V ±10 %)
2)
A
240
302
361
477
515
590
• Base-load current
I
H
(400 V ±10 %)
3)
A
240
296
368
468
491
551
• Base-load current
I
H
(480 V ±10 %)
3)
A
196
247
295
390
394
452
• Max. output current
I
max
A
392
486
608
770
864
972
Rated pulse frequency
kHz
2
2
2
2
2
2
Input current
4)
• Rated current
I
rated
(400 V ±10 %)
A
317
375
469
597
668
750
• Rated current
I
rated
(480 V ±10 %)
A
262
314
376
497
536
614
• Base-load current
I
L
(400 V ±10 %)
2)
A
307
365
459
585
654
735
• Base-load current
I
L
(480 V ±10 %)
2)
A
257
308
368
486
525
602
• Base-load current
I
H
(400 V ±10 %)
3)
A
254
300
375
477
501
562
• Base-load current
I
H
(480 V ±10 %)
3)
A
210
251
301
397
402
461
• Max. input current
A
415
493
620
785
881
992
Short-circuit current rating
according to IEC
in conjunction with the specified fuses
kA
100
100
100
100
100
100
Rated short-circuit current SCCR
(Short-Circuit Current Rating)
in accordance with UL508C
(up to 600 V)
in conjunction with the specified fuses
kA
100
100
100
100
100
100
Minimum short-circuit current
5)
• For 3NE1 fuses
A
3500
4500
7000
10000
11000
13000
• For 3NA3 fuses
A
9500
14000
20000
20000
30000
30000
Efficiency
η
At rated current
I
rated
(400 V/45 °C (113 °F))
%
98
98
98.1
98.1
98
98.1
Power loss
At rated current
I
rated
(400 V/45 °C (113 °F))
kW
3.642
4.414
5.125
6.791
7.687
8.385
Coolant requirements
m
3
/s (ft
3
/s)
0.21 (7.42)
0.21 (7.42)
0.21 (7.42)
0.36 (12.7)
0.36 (12.7)
0.36 (12.7)
Coolant
Air
Air
Air
Air
Air
Air
Sound pressure level
L
pA
(1 m)
dB
74
74
74
74
74
74
Power requirement 24 V DC supply
A
0.5
0.5
0.5
0.5
0.5
0.5
1)
Rated power of a typical 4-pole standard induction motor based on the
base-load current
I
L
or
I
H
at 400 V 3 AC/50 Hz (kW) or 460 V 3 AC/60 Hz
(hp).
2)
The base-load current
I
L
is based on the duty cycle for low overload (LO).
3)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
4)
The input current depends on the motor load and line impedance and
applies for a line impedance corresponding to
u
K
= 1 %. The rated input
currents apply for a load at rated power (based on
I
rated
) – these current
values are specified on the rating plate.
5)
10 ms value from current-time characteristic for reliable tripping of installed
protection devices. If the minimum short-circuit current is not reached, the
tripping time of the fuses is increased, which can lead to damage.
© Siemens AG 2017