SIEMENS
4/53
Siemens D 35 · 2017
4
SINAMICS G120P built-in and wall-mounted units
PM240P-2 Power Modules, 11 kW to 132 kW
Recommended line-side power components
■
Selection and ordering data
The following table lists recommendations for additional line-
side components, such as fuses and circuit breakers. The val-
ues in the table take into account the overload capability of the
inverter.
Notes
for use in compliance with IEC standards:
3NA3 or 3NE1 fuses and 3RV motor starter protectors or 3VL cir-
cuit breakers are recommended for European countries.
Notes
for use in compliance with UL regulations:
UL-listed fuses Class J or 3NE1 with 600 V AC rated voltage
(UL-compliant – corresponds to
U
) are required for North
America.
Short-Circuit Current Rating SCCR
(Short-Circuit Current Rating) according to UL
Applies to industrial control panel installations acc. to
NEC article 409 or UL 61800-5-1.
•
PM240P-2: 65 kA
Notes
regarding installations in Canada:
Overvoltage protection devices in accordance with overvoltage
category III and with the following ratings must be connected on
the line side of the inverter:
•
Rated voltage 480 V/600 V (phase-phase), 480 V/600 V
(phase-to-ground) at a rated line voltage of 480 V/600 V
•
Voltage limit 4 kV (phase-phase) and 6 kV (phase-ground)
All overvoltage protection devices used must comply with
Canadian standards for industrial installations.
Additional information about the listed fuses and circuit breakers
is available in Catalogs LV 10, IC 10 and IC 10 AO.
Rated power
1)
SINAMICS G120
PM240P-2
Power Modules
IEC-compliant
UL/cUL-compliant
Fuse
Circuit breaker
Fuse
Fuse type
Rated voltage
600 V AC
400 V/690 V
460 V/575 V
Type
Current
Type 3NA3
Type 3NE1 (
U
)
Current
kW
hp
6SL3210-...
Frame size
A
Article No.
Article No.
Article No.
Class
A
380 ... 480 V 3 AC
22
25
1RE24-5 . L0
FSD
80
3NA3824
3RV1041-4KA10
3NE1820-0
J
70
30
30
1RE26-0 . L0
FSD
100
3NA3830
3RV1041-4LA10
3NE1021-0
J
90
37
40
1RE27-5 . L0
FSD
100
3NA3830
3RV1041-4MA10
3NE1021-0
J
100
45
50
1RE28-8 . L0
FSE
125
3NA3832
3VL1712-2DD33-….
*)
3NE1022-0
J
125
55
60
1RE31-1 . L0
FSE
160
3NA3836
3VL1716-2DD33-….
*)
3NE1224-0
J
150
75
75
1RE31-5 . L0
FSF
200
3NA3140
3VL3720-3DC33-….
*)
3NE1225-0
J
200
90
100
1RE31-8 . L0
FSF
224
3NA3142
3VL3725-3DC33-….
*)
3NE1227-0
J
225
110
125
1RE32-1 . L0
FSF
300
3NA3250
3VL4731-3DC36-….
*)
3NE1230-0
J
300
132
150
1RE32-5 . L0
FSF
315
3NA3252
3VL4740-3DC36-….
*)
3NE1331-0
J
350
500 ... 690 V 3 AC
11
10
1RH21-4 . L0
FSD
50
3NA3120-6
3RV1042-4BA10
3NE1815-0
J
20
15
15
1RH22-0 . L0
FSD
50
3NA3120-6
3RV1042-4EA10
3NE1815-0
J
25
18.5
20
1RH22-3 . L0
FSD
50
3NA3120-6
3RV1042-4EA10
3NE1803-0
J
30
22
25
1RH22-7 . L0
FSD
50
3NA3120-6
3VL1704-2DD33-….
*)
3NE1803-0
J
35
30
30
1RH23-5 . L0
FSD
50
3NA3120-6
3VL1705-2DD33-….
*)
3NE1817-0
J
45
37
40
1RH24-2 . L0
FSD
63
3NA3122-6
3VL1706-2DD33-….
*)
3NE1818-0
J
60
45
50
1RH25-2 . L0
FSE
80
3NA3124-6
3VL1708-2DD33-….
*)
3NE1820-0
J
80
55
60
1RH26-2 . L0
FSE
80
3NA3124-6
3VL1710-2DD33-….
*)
3NE1820-0
J
80
75
75
1RH28-0 . L0
FSF
100
3NA3130-6
3VL1712-2DD33-….
*)
3NE1021-0
J
100
90
100
1RH31-0 . L0
FSF
125
3NA3132-6
3VL1712-2DD33-….
*)
3NE1022-0
J
125
110
100
1RH31-2 . L0
FSF
160
3NA3136-6
3VL1716-2DD33-….
*)
3NE1224-0
J
150
132
125
1RH31-4 . L0
FSF
200
3NA3140-6
3VL3720-3DC33-….
*)
3NE1225-0
J
200
1)
Rated power based on the rated output current
I
rated
. The rated output
current
I
rated
is based on the duty cycle for low overload (LO).
*)
See Catalog LV 10 for Article No. supplements.