Characteristic curves
(continued)
4
SINAMICS G120P built-in and wall-mounted units
PM240P-2 Power Modules, 11 kW to 132 kW
PM240P-2 Power Modules
Current derating as a function of the ambient temperature
Permissible output current as a function of the ambient temperature for
low overload (LO) and high overload (HO)
Note:
The operating temperature ranges of the Control Units should be
taken into account.
The temperature ranges are specified in the
section Technical specifications under Control Units.
Current derating as a function of the installation altitude
Permissible line supplies as a function of the installation altitude
•
Installation altitude up to 2000 m (6562 ft) above sea level
-
Connection to every supply system permitted for the inverter
•
Installation altitudes between 2000 m (6562 ft) and 4000 m
(13124 ft) above sea level
- Connection to a TN system with grounded neutral point
- TN systems with grounded line conductor are not permitted
- The TN line system with grounded neutral point can also be
supplied using an isolation transformer
- The phase-to-phase voltage does not have to be reduced
Permissible output current as a function of the installation altitude
Note:
The connected motors, power elements and components must
be considered separately.
Current derating as a function of the installation altitude and the ambient temperature
At installation altitudes above 1000 m (3281 ft), the permissible output current can be compensated to a certain extent using the
ambient temperature.
G_D011_EN_00503
Ambient temperature
I
H
I
L
Permissible
output current
°C
%
100
50
25
0
0
10
20
30
40
50
60
75
74
85
66
Installation altitude above sea level
Permissible
output current
m
G_D011_EN_00504
60
90
70
4000
3000
2000
1000
0
100
80
%
Installation altitude
above sea level
Current derating factor (in % of the base-load output current I
L
) at an ambient temperature of
m (ft)
0 °C
(32 °F)
5 °C
(41 °F)
10 °C
(50 °F)
15 °C
(59 °F)
20 °C
(68 °F)
25 °C
(77 °F)
30 °C
(86 °F)
35 °C
(95 °F)
40 °C
(104 °F)
45 °C
(113 °F)
50 °C
(122 °F)
55 °C
(131 °F)
60 °C
(140 °F)
0 ... 1000 (0 ... 3281)
93 %
85 %
76 %
66 %
1000 ... 1500 (3281 ...
4921)
95 %
88 %
81 %
72 %
63 %
1500 ... 2000 (4921 ... 6562)
100 %
97 %
90 %
83 %
77 %
68 %
59 %
2000 ... 2500 (6562 ... 8202)
98 %
91 %
85 %
79 %
72 %
64 %
56 %
2500 ... 3000 (8202 ... 9843)
98 %
92 %
86 %
80 %
74 %
68 %
60 %
53 %
3000 ... 3500 (9843 ... 11483)
98 %
98 %
98 %
98 %
98 %
92 %
86 %
81 %
75 %
69 %
64 %
57 %
50 %
3500 ... 4000 (11483 ... 13123)
91 %
91 %
91 %
91 %
91 %
86 %
81 %
75 %
70 %
65 %
60 %
53 %
46 %
Installation altitude
above sea level
Current derating factor (in % of the base-load output current I
H
) at an ambient temperature of
m (ft)
0 °C
(32 °F)
5 °C
(41 °F)
10 °C
(50 °F)
15 °C
(59 °F)
20 °C
(68 °F)
25 °C
(77 °F)
30 °C
(86 °F)
35 °C
(95 °F)
40 °C
(104 °F)
45 °C
(113 °F)
50 °C
(122 °F)
55 °C
(131 °F)
60 °C
(140 °F)
0 ... 1000 (0 ... 3281)
87 %
74 %
1000 ... 1500 (3281 ...
4921)
95 %
83 %
70 %
1500 ... 2000 (4921 ... 6562)
100 %
99 %
95 %
90 %
78 %
67 %
2000 ... 2500 (6562 ... 8202)
98 %
94 %
89 %
85 %
74 %
63 %
2500 ... 3000 (8202 ... 9843)
96 %
92 %
88 %
84 %
80 %
70 %
59 %
3000 ... 3500 (9843 ... 11483)
98 %
98 %
98 %
98 %
98 %
94 %
90 %
86 %
83 %
79 %
75 %
65 %
56 %
3500 ... 4000 (11483 ... 13123)
91 %
91 %
91 %
91 %
91 %
88 %
84 %
81 %
77 %
74 %
70 %
61 %
52 %