SIEMENS
4/45
Siemens D 35 · 2017
■
Technical specifications
(continued)
4
SINAMICS G120P built-in and wall-mounted units
PM240P-2 Power Modules, 11 kW to 132 kW
PM240P-2 Power Modules
PM240P-2 Power Modules
Line voltage 380 ... 480 V 3 AC
PM240P-2 Power Modules
Without integrated line filter
6SL3210-
1RE24-5UL0
6SL3210-
1RE26-0UL0
6SL3210-
1RE27-5UL0
6SL3210-
1RE28-8UL0
6SL3210-
1RE31-1UL0
With integrated line filter
6SL3210-
1RE24-5AL0
6SL3210-
1RE26-0AL0
6SL3210-
1RE27-5AL0
6SL3210-
1RE28-8AL0
6SL3210-
1RE31-1AL0
Output current
at 50 Hz 400 V 3 AC
• Rated current
I
rated
1)
A
45
60
75
90
110
• Base-load current
I
L
1)
A
45
60
75
90
110
• Base-load current
I
H
2)
A
38
45
60
75
90
• Maximum current
I
max
A
61
81
102
122
149
Rated power
• Based on
I
L
kW
22
30
37
45
55
• Based on
I
H
kW
18.5
22
30
37
45
Rated pulse frequency
kHz
4
4
4
4
4
Efficiency
η
%
98
98
98
98
98
Power loss
3)
at rated current
• Without integrated line filter
kW
0.7
0.85
1.12
1.25
1.59
• With integrated line filter
kW
0.71
0.85
1.12
1.28
1.63
Cooling air requirement
m
3
/s (ft
3
/s)
0.055 (1.94)
0.055 (1.94)
0.055 (1.94)
0.083 (2.93)
0.083 (2.93)
Sound pressure level
L
pA
(1 m)
dB
71.6
71.6
71.6
70.6
70.6
24 V DC power supply
for Control Unit
A
1
1
1
1
1
Rated input current
I
rated
4)
42
57
70
86
104
Line supply connection
U1/L1, V1/L2, W1/L3
Screw-type terminal
Screw-type terminal
Screw-type terminal
Screw-type terminal
Screw-type terminal
• Conductor cross-section
mm
2
10 ... 35
10 ... 35
10 ... 35
25 ... 70
25 ... 70
Motor connection
U2, V2, W2
Screw-type terminal
Screw-type terminal
Screw-type terminal
Screw-type terminal
Screw-type terminal
• Conductor cross-section
mm
2
10 ... 35
10 ... 35
10 ... 35
25 ... 70
25 ... 70
Feedback connection
F3, R1
Screw-type terminal
Screw-type terminal
Screw-type terminal
Screw-type terminal
Screw-type terminal
• Conductor cross-section
mm
2
10 ... 35
10 ... 35
10 ... 35
25 ... 70
25 ... 70
PE connection
Screw-type terminal
Screw-type terminal
Screw-type terminal
Screw-type terminal
Screw-type terminal
• Conductor cross-section
mm
2
10 ... 35
10 ... 35
10 ... 35
25 ... 70
25 ... 70
Motor cable length
5)
, max.
• Shielded
m (ft)
200 (656)
200 (656)
200 (656)
200 (656)
200 (656)
• Unshielded
m (ft)
300 (984)
300 (984)
300 (984)
300 (984)
300 (984)
Degree of protection
IP20
IP20
IP20
IP20
IP20
Dimensions
• Width
mm (in)
200 (7.87)
200 (7.87)
200 (7.87)
275 (10.8)
275 (10.8)
• Height
mm (in)
472 (18.6)
472 (18.6)
472 (18.6)
551 (21.7)
551 (21.7)
• Depth
-
Without operator panel
mm (in)
237 (9.33)
237 (9.33)
237 (9.33)
237 (9.33)
237 (9.33)
-
With Control Unit and operator panel,
max.
mm (in)
274.5 (10.8)
274.5 (10.8)
274.5 (10.8)
274.5 (10.8)
274.5 (10.8)
Frame size
FSD
FSD
FSD
FSE
FSE
Weight, approx.
• Without integrated line filter
kg (lb)
16.6 (36.6)
18.3 (40.3)
18.3 (40.3)
26 (57.3)
26 (57.3)
• With integrated line filter
kg (lb)
18.3 (40.3)
19 (41.9)
19 (41.9)
28 (61.7)
28 (61.7)
1)
The rated output current
I
rated
and the base-load current
I
L
are based on
the duty cycle for low overload (LO).
2)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
3)
Maximum values. You can find more information on the Internet at
4)
The input current depends on the motor load and line impedance. The
input currents apply for a load at rated power (based on
I
rated
) for a line
impedance corresponding to
u
K
= 1 %.
5)
The specified cable lengths apply to Power Modules without output option
and without compliance with the limit values for RI suppression.
© Siemens AG 2017