SIEMENS
4/44
Siemens D 35 · 2017
4
SINAMICS G120P built-in and wall-mounted units
PM240P-2 Power Modules, 11 kW to 132 kW
PM240P-2 Power Modules
■
Technical specifications
General technical specifications
PM240P-2 Power Modules
System operating voltage
380 ... 480 V 3 AC ±10 % (in operation -20 % < 1 min)
500 ... 690 V 3 AC ±10 % (in operation -20 % < 1 min)
Grid requirement
Short-circuit power R
SC
>25
Input frequency
47 ... 63 Hz
Output frequency
• Control mode V/f
0 ... 550 Hz
• Control type Vector
0 ... 200 Hz
Pulse frequency
• At 380 ... 480 V 3 AC ±10 %
up to 90 kW (121 hp) (LO): 4 kHz
from 110 kW (148 hp) (LO): 2 kHz
Higher pulse frequencies up to 16 kHz,
see derating data
• At 500 ... 690 V 3 AC ±10 %
2 kHz, can be adjusted to 4 kHz
Power factor
λ
0.95 at 380 ... 480 V 3 AC
0.9 at 500 ... 690 V 3 AC
Offset factor cos
ϕ
0.99
Inverter efficiency
>97 % at 380 ... 480 V 3 AC
>98 % at 500 ... 690 V 3 AC
Output voltage, max.
As % of input voltage
95 %
Overload capability
• Low overload (LO)
Note:
When the overload capability is used,
the base-load current
I
L
is not reduced.
1.35 × base-load current
I
L
(i.e. 135 % overload) for 3 s
plus
1.1 × base-load current
I
L
(i.e. 110 % overload)
for 57 s within a cycle time of 300 s
• High overload (HO)
Note:
When the overload capability is used,
the base-load current
I
H
is not reduced.
1.5 × base-load current
I
H
(i. e. 150 % overload) for 60 s within a cycle time of 300 s
Electromagnetic compatibility
• Devices without line filter
• Devices with line filter class A for compliance with conducted and radiated interference requirements of
Category C2
Possible braking methods
• DC braking
• Compound braking
Degree of protection
IP20
Operating temperature
• Low overload
(LO)
-20 ... +40 °C (-4 ... +104 °F) without derating
>40 ... 60 °C (>104 ... 140 °F)
see derating characteristics
• High overload
(HO)
-20 ... +50 °C (-4 ... +122 °F) without derating
>50 ... 60 °C (>122 ... 140 °F)
see derating characteristics
Relative humidity
5 … 95 %, condensation not permitted
Storage temperature
-25 ... +55 °C (-13 ... +131 °F)
Cooling
Internal ventilation, power units with increased air cooling by built-in fans
Installation altitude
Up to 1000 m (3281 ft) above sea level without derating,
> 1000 m (3281 ft)
see derating characteristics
Protection functions
• Undervoltage
• Overvoltage
• Overcurrent/overload
• Overtemperature
• Ground fault
• Short-circuit
• Stall protection
• Motor blocking protection
• Motor overtemperature
• Inverter overtemperature
• Parameter locking
Short-Circuit Current Rating SCCR
(Short-Circuit Current Rating)
1)
65 kA
Compliance with standards
UL, cUL, CE, RCM, SEMI F47
CE marking
According to Low Voltage Directive 2014/35/EU, EMC Directive 2014/30/EU
1)
Applies to industrial control panel installations to NEC article 409 or
UL 61800-5-1.
© Siemens AG 2017