SIEMENS
4/43
Siemens D 35 · 2017
■
Integration
(continued)
4
SINAMICS G120P built-in and wall-mounted units
PM240P-2 Power Modules, 11 kW to 132 kW
PM240P-2 Power Modules
Maximum permissible cable lengths from the motor
to the inverter when using output reactors or dv/dt filters
depending on the voltage range
The following load-side power components in the appropriate
frame sizes are optionally available for the Power Modules and
result in the following maximum cable lengths:
■
Selection and ordering data
To ensure that a suitable Power Module is selected, the following
currents should be used for applications:
•
Rated output current for applications with low overload
(LO)
•
Base-load current for applications with high overload (HO)
With reference to the rated output current, the modules support
at least 2-pole to 6-pole low-voltage motors, e.g. the
SIMOTICS GP and SIMOTICS SD 1LE1 motor series. The rated
power is merely a guide value. For a description of the overload
performance, please refer to the general technical specifica-
tions of the Power Modules.
PM240P-2 Power Modules
Note:
The power data in hp units is based on the NEC/CEC standards
for the North American market.
PM240P-2
Power Module,
frame sizes FSD and FSE
System operating
voltage
Maximum permissible
motor cable lengths
(shielded/unshielded)
in m (ft)
Without output option
380 ... 480 V 3 AC
200/300 (656/984)
Without output option,
compliance with
Category C2 acc. to
EN 61800-3
380 ... 480 V 3 AC
150/- (492/-)
With two output reactors
in series
380 ... 480 V 3 AC
350/525 (1148/1722)
With dv/dt filter plus VPL
500 ... 690 V 3 AC
300/450 (984/1476)
PM240P-2
Power Module,
frame size FSF
System operating
voltage
Maximum permissible
motor cable lengths
(shielded/unshielded)
in m (ft)
Without output option
380 ... 480 V 3 AC
500 ... 690 V 3 AC
300/450 (984/1476)
300/450 (984/1476)
Without output option,
compliance with
Categories C2 and/or C3
acc. to EN 61800-3
380 ... 480 V 3 AC
500 ... 690 V 3 AC
150/- (Category C2)
150/- (Category C3)
With two output reactors
in series
380 ... 480 V 3 AC
500 ... 690 V 3 AC
525/800 (1722/2625)
525/800 (1722/2625)
With dv/dt filter plus VPL
500 ... 690 V 3 AC
300/450 (984/1476)
Rated power
1)
Rated output
current
I
rated
2)
Power
based on the
base-load current
3)
Base-load
current
I
H
3)
Frame size
PM240P-2 Power Module
without
integrated line filter
PM240P-2 Power Module
with
integrated line filter
class A
400 V/
690 V
460 V/
575 V
400 V/
690 V
460 V/
575 V
kW
hp
A
kW
hp
A
Article No.
Article No.
380 ... 480 V 3 AC
22
25
45
18.5
20
38
FSD
6SL3210-1RE24-5UL0
6SL3210-1RE24-5AL0
30
30
60
22
25
45
FSD
6SL3210-1RE26-0UL0
6SL3210-1RE26-0AL0
37
40
75
30
30
60
FSD
6SL3210-1RE27-5UL0
6SL3210-1RE27-5AL0
45
50
90
37
40
75
FSE
6SL3210-1RE28-8UL0
6SL3210-1RE28-8AL0
55
60
110
45
50
90
FSE
6SL3210-1RE31-1UL0
6SL3210-1RE31-1AL0
75
75
145
55
60
110
FSF
6SL3210-1RE31-5UL0
6SL3210-1RE31-5AL0
90
100
178
75
75
145
FSF
6SL3210-1RE31-8UL0
6SL3210-1RE31-8AL0
110
125
205
90
100
178
FSF
6SL3210-1RE32-1UL0
6SL3210-1RE32-1AL0
132
150
250
110
125
205
FSF
6SL3210-1RE32-5UL0
6SL3210-1RE32-5AL0
500 ... 690 V 3 AC
11
10
14
7.5
8
11
FSD
6SL3210-1RH21-4UL0
6SL3210-1RH21-4AL0
15
15
19
11
10
14
FSD
6SL3210-1RH22-0UL0
6SL3210-1RH22-0AL0
18.5
20
23
15
15
19
FSD
6SL3210-1RH22-3UL0
6SL3210-1RH22-3AL0
22
25
27
18.5
20
23
FSD
6SL3210-1RH22-7UL0
6SL3210-1RH22-7AL0
30
30
35
22
25
27
FSD
6SL3210-1RH23-5UL0
6SL3210-1RH23-5AL0
37
40
42
30
30
35
FSD
6SL3210-1RH24-2UL0
6SL3210-1RH24-2AL0
45
50
52
37
40
42
FSE
6SL3210-1RH25-2UL0
6SL3210-1RH25-2AL0
55
60
62
45
50
52
FSE
6SL3210-1RH26-2UL0
6SL3210-1RH26-2AL0
75
75
80
55
60
62
FSF
6SL3210-1RH28-0UL0
6SL3210-1RH28-0AL0
90
100
100
75
75
80
FSF
6SL3210-1RH31-0UL0
6SL3210-1RH31-0AL0
110
100
115
90
100
100
FSF
6SL3210-1RH31-2UL0
6SL3210-1RH31-2AL0
132
125
142
110
100
115
FSF
6SL3210-1RH31-4UL0
6SL3210-1RH31-4AL0
1)
Rated power based on the rated output current
I
rated
. The rated output
current
I
rated
is based on the duty cycle for low overload (LO).
2)
The rated output current
I
rated
is based on the duty cycle for low overload
(LO). These current values are valid for 400 V or 690 V and are specified
on the rating plate of the Power Module.
3)
The base-load current
I
H
is based on the duty cycle for high overload
(HO).
© Siemens AG 2017