SIEMENS
4/39
Siemens D 35 · 2017
■
Technical specifications
(continued)
4
SINAMICS G120P built-in and wall-mounted units
PM230 Power Modules, 0.37 kW to 90 kW
Output reactors
Line voltage 380 ... 480 V 3 AC
Output reactor
6SE6400-3TC14-5FD0
6SE6400-3TC15-4FD0
6SE6400-3TC14-5FD0
Rated current
A
178
1)
178
1)
178
1)
Power loss
kW
0.47
0.25
0.47
Connection to the Power Module
Flat connector for M8 cable lug
Flat connector for M8 cable lug
Flat connector for M8 cable lug
Motor connection
Flat connector for M8 cable lug
Flat connector for M8 cable lug
Flat connector for M8 cable lug
PE connection
M8 screw
M6 screw
M8 screw
Cable length, max.
between output reactor and motor
• 380 V -10 % ... 480 V +10 % 3 AC
- Shielded
m (ft)
200 (656)
200 (656)
200 (656)
- Unshielded
m (ft)
300 (984)
300 (984)
300 (984)
Dimensions
• Width
mm (in)
350 (13.78)
270 (10.63)
350 (13.78)
• Height
mm (in)
321 (12.64)
248 (9.76)
321 (12.64)
• Depth
mm (in)
288 (11.34)
209 (8.23)
288 (11.34)
Possible as base component
No
No
No
Degree of protection
IP00
IP00
IP00
Weight, approx.
kg (lb)
51.5 (114)
24 (52.9)
51.5 (114)
Suitable for
PM230 Power Module
degree of protection IP20
Type
6SL3210-1NE31-1UL0
6SL3210-1NE31-1AL0
6SL3210-1NE31-5UL0
6SL3210-1NE31-5AL0
–
Suitable for
PM230 Power Module
degree of protection IP55/
UL Type 12
Type
6SL3223-0DE35-5UA0
6SL3223-0DE35-5AA0
6SL3223-0DE37-5UA0
6SL3223-0DE37-5AA0
6SL3223-0DE38-8UA0
6SL3223-0DE38-8AA0
• Rated power of the Power Module
kW
55
75
90
• Rated current
I
rated
of the
Power Module
A
110
145
178
• Frame size
FSF
FSF
FSF
1)
On the rating plate of the reactor the current is specified according to the
duty cycle for high overload (HO). This is lower than the current specified
according to the duty cycle for low overload (LO) of the Power Module.
© Siemens AG 2017