SINAMICS DCM
DC Converter and Control Module
DC Converter
3/45
Siemens D 23.1 · 2014
3
■
Circuit diagrams
(continued)
Assignment, terminal X177 (continued)
Terminal
X177
Function
Technical data
Pulse encoder input
41
Pulse encoder supply
+13.7 … +15.2 V, 300 mA short-circuit proof (electronically protected)
For overload: Alarm A60018
42
Pulse encoder ground
43
Track 1 positive connection
Load:
≤
5.25 mA at 15 V (without switching losses)
Pulse duty factor: 1:1
See below for data relating to cables, cable length, shield connection,
input pulse levels, hysteresis, track displacement, and pulse
frequency.
44
Track 1 negative connection
45
Track 2 positive connection
46
Track 2 negative connection
47
Zero mark positive connection
48
Zero mark negative connection
Analog outputs (user-assignable outputs)
49
AO0
Analog output 0
±
10 V, max. 2 mA short-circuit proof, resolution
±
15 bits
50
M
Ground, analog
51
AO1
Analog output 1
52
M
Ground, analog
Connections for temperature sensor (motor interface 1)
53
Temp 1
Sensor acc. to p50490
The cable to the temperature sensor on the motor must be shielded
and connected to ground at both ends.
The cables for the Temp 1 and Temp 3 connections to the temperature
sensor must have approximately the same length.
The sense cable (Temp 2) is used for compensating the cable
resistances. If you are not using a sense cable, terminals 54 and 55
must be connected.
54
Temp 2 (sense cable)
55
Temp 3
56
M
Ground, analog
Connector Board