SIEMENS
SINAMICS DCM
Accessories and supplementary components
SIMOREG CCP
4/33
Siemens D 23.1 · 2014
4
■
Technical specifications
SIMOREG CCP
Type
6RA7085-6FC00-0
6RA7091-6FC00-0
6RA7095-6FC00-0
6RA7090-6KC00-0
6RA7095-6KC00-0
Rated voltage
V
460 (+15 %/–20 %)
690 (+10 %/–20 %)
Rated current
A
600
1200
2000
1000
2000
Current range that can be
covered
1)
A
up to 600
up to 1200
up to 2000
up to 1000
up to 2000
Rated supply voltage,
electronics power supply
V
380 (–20 %) … 60 (+15 %) 2 AC;
I
n
= 1 A or
190 (–20 %) … 230 (+15 %) 1 AC;
I
n
= 2 A
Rated frequency
Hz
45 ... 65
Power loss
W
100
Ambient temperature
• Operation
°C
0 ... 55
• Storage and transport
°C
–25 ... +70
Installation altitude above
sea level
m
≤
1000 m
Climate class
3K3 acc. to EN 60721-3-3
Degree of pollution
2 acc. to EN 50178
2)
Degree of protection
IP00 acc. to EN 60529
Dimensions
• Width
mm
406
• Height
mm
780
• Depth
mm
500
Weight, approx.
kg
35
35
55
45
75
Fuse for connections
1U1, 1V1, 1W1 and 1D1
3NA3365-6
1 each
3NA3365-6
1 each
3NA3365-6
2 each in parallel
3NA3365-6
1 each
3NA3365-6
2 each in parallel
Fuse for connections
2U1, 2V1, 2W1
(10 A cable protection)
DIAZED 5SD604
1)
The current range that can be covered corresponds to the actual rated
current of the SINAMICS DC MASTER. When the rated current is reduced
(via parameter) then the lower value obtained applies. This means that for a
SINAMICS DC MASTER with (according to the rating plate) a rated current
higher than 2000 A (necessary e.g. to maintain longer specified overload
times), it is possible to use the CCP if the actual rated current, specified by
the parameterization, does not exceed 2000 A. The possible overload
capability of 1.8x the actual rated current can be additionally utilized.
2)
Definition of pollution degree 2:
Generally only non-conductive pollution occurs. However, occasionally
conductive pollution can be expected for a short period of time if the
electronic equipment is not operational.
© Siemens AG 2014