SIEMENS
SINAMICS DCM
Accessories and supplementary components
Commutating reactors
4/19
Siemens D 23.1 · 2014
4
■
Selection and ordering data
1)
Note:
The commutating reactors are dimensioned according to the rated motor current in the armature and field circuits. When the unit is
connected to a single phase, single-phase commutating reactors must also be used in the armature circuit. These are available on
request.
The tables below list the commutating reactors which are available as standard.
Additional information can be found in the Operating Instructions "SINAMICS DCM Commutation reactors" (see
).
Note:
Commutating reactors with
u
K
= 2 % are available on request. A
limited tolerance range is also possible for parallel connections.
General technical specifications
Degree of protection
IP00
Protection class
Class 1
2)
Cooling
AN, self-ventilated
Inductance tolerance
± 10 %
Environmental classes according to DIN IEC 60721-3, Parts 1 to 3
• Climatic:
- Storage
:
1K3
- Transport
:
2K2
- Operation
:
3K3
• Mechanical: 3M3
Ambient temperature during operation
• 1-phase reactors
0 to +45 °C, above with derating
• 3-phase reactors
0 to +40 °C, above with derating
Ambient temperature for storage and transport
-40 to +70 °C
Installation altitude (at rated current)
≤
1000 m above sea level, above with derating
Operation at 50 Hz and 60 Hz with rated current is permissible
Three-phase commutating reactors,
u
K
= 4 %
AC rated
current
Inductance
Copper losses
Total losses
Short-circuit
current rating
(SCCR)
Weight
Rated
insulation
voltage
Article No.
A
mH
W
W
kA
kg
V
Rated voltage 400 V
13
2.315
22.8
33.1
2.0 (20 ms)
2.9
600
6RX1800-4DK00
25
1.158
30.8
53.2
5.0 (20 ms)
4.4
600
6RX1800-4DK01
51
0.579
43.5
73.2
6.5 (100 ms)
10.9
600
6RX1800-4DK02
76
0.386
64.4
118.5
9.0 (100 ms)
13.8
600
6RX1800-4DK03
106
0.278
51.3
119.3
15 (100 ms)
23.9
600
6RX1800-4DK04
174
0.169
164.8
206.4
15 (100 ms)
24.0
600
6RX1800-4DK05
232
0.127
197.4
256.2
20 (100 ms)
26.8
600
6RX1800-4DK06
332
0.089
190.7
251.1
24 (200 ms)
45.8
600
6RX1800-4DK07
374
0.079
186.7
251.7
24 (200 ms)
56.8
600
6RX1800-4DK08
498
0.059
277.0
357.4
35 (200 ms)
60.0
600
6RX1800-4DK10
706
0.042
329.4
424.8
55 (200 ms)
81.6
1000
6RX1800-4DK11
996
0.030
390.3
562.8
75 (200 ms)
100.1
1000
6RX1800-4DK12
1328
0.022
339.3
554.5
75 (200 ms)
138.8
1000
6RX1800-4DK13
1660
0.018
369.3
591.9
75 (200 ms)
210.7
1000
6RX1800-4DK14
2490
0.012
587.3
1038.3
75 (200 ms)
205.6
1000
6RX1800-4DK15
1)
All commutating reactors with rated voltages
V
N
≤
600 V to UL
2)
Note about protection class 1:
Despite protective conductor connection, no 'touchable conductive parts'
with regard to the standard (e.g. EN 61800-5-1) are defined. In this case,
the protective conductor ensures that no dangerous voltages/currents can
act at the mounting surfaces. The complete reactor must be considered as
being an active component.
© Siemens AG 2014