Description of Options
M17
Electrical door interlocks
The electrical switch doors interlock removes power from
energized sectors.
Drive sends a signal to the circuit breaker trip circuit to
remove power and to prevent closure of the circuit breaker.
This system prevents the drive from being energized until all
doors into the energized sections in the drive are closed.
This system is a backup to the mechanical door interlocks
(M08, M09, M10, and M38).
Note:
M17
is included by option U02 (Version with CE
conformity. It is not available separately for these drives.
This system is a backup to the mechanical door interlocks
(
M08, M09, M10,
and
M38
).
M36, M37
Gland plates
With options
M36
and
M37
, gland plates can be ordered in
a brass (
M36
) and stainless steel (
M37
) version.
The options M36 and M37 are mutually exclusive.
Option
Description
M36
Gland plates, brass
M37
Gland plates, stainless steel
Note: Options M36 and M37 apply for input/output
power cables only. Gland plates for control cables are always
aluminum.
N26
Synchronized pre-charge pre-magnetization of
the transformer
Liquid-cooled Perfect Harmony drives come equipped as
standard with an asynchronous pre-charge system that
will bring the DC-link capacitors in all power cells up to rated
voltage before the incoming circuit-breaker is closed.
Even with all the power cells pre-energized, the input
transformer will still draw the characteristic inrush currents
associated with distribution transformers of this size
when energized.
The synchronized pre-charge option allows not only the
DC-link capacitors in all power cells to be pre-charged, but
in addition, to build-up the input transformer flux in close
phase relation with the incoming medium voltage feed,
hence minimizing the transformer inrush currents when
the circuit-breaker is closed.
N85
Operator panel located internal to cabinet
Operator panel installed on the control panel inside the
drive cabinet, no touchscreen provided.
T03, T04
Nameplate color, material
Option
Description
T03
White letters with black core
(standard: black letters, white core)
T04
Stainless steel
(standard: phenolic)
T74 to T91
Nameplate languages
Nameplates can be supplied in two languages. The following
order codes provide a list of available languages.
Note: Please contact the factory or local Siemens sales
representative for languages different from the ones
specified below.
Option
Description
T74
English / German
T82
English / Portuguese (Brazil)
T85
English / Russian
T91
English / Chinese
Table 3-6 Mutually exclusive options T74 to T91
Nameplate language
Code
T74
T82
T85
T91
English / German
T74
―
―
―
English / Portuguese (Brazil)
T82
―
―
―
English / Russian
T85
―
―
―
English / Chinese
T91
―
―
―
—
Options are mutually exclusive.
U02
Version with CE conformity
With option
U02
, a drive version with CE conformity
is supplied.
Note: Option
U02
includes options
L03
(EMC filter) and
M08
(mechanical door interlocks – Superior).