SIEMENS
ROBICON Perfect Harmony
Liquid-cooled drives
3
3/18
Siemens D 16.2 – 2012
ROBICON Perfect Harmony
liquid-cooled drive version
6SR3252-
3.B48-0..0
6SR3252-
3.B48-5..0
6SR3252-
3.B48-7..0
6SR3252-
3.B48-8..0
6SR3252-
3.B52-0..0
Motor voltage 6.9/7.2 kV
Max. output voltage
kV
8.0
8.0
8.0
8.0
8.0
Type rating
kVA
9660
10540
10970
11420
12300
Shaft output
1)
hp
kW
11000
8206
12000
8952
12492
9319
13000
9698
14000
10444
Typical motor current
1)
A
774.89
845.34
880.00
915.78
986.23
Power cell current
A
880
880
880
1250
1250
Number of cells
18
18
18
18
18
Transformer rating
kVA
11000
12000
13000
13000
14000
Power losses of drive system
• Copper transformer
kW
< 385
< 420
< 455
< 455
< 490
Efficiency P
out
/P
in
2)
of
drive system
• Copper transformer
%
96.5
96.5
96.5
96.5
96.5
Auxiliary supply
• Single-phase w/o options
3)
kVA
2.5
2.5
2.5
2.5
2.5
• Single-phase w/ all options
3)
kVA
2.5
2.5
2.5
2.5
2.5
• Three-phase w/o CPT
4)
kVA
25
25
25
25
25
• Three-phase w/ CPT and all
-options
4)
kVA
27.5
27.5
27.5
27.5
27.5
System pre-charge
5)
%
< 0.5
< 0.5
< 0.5
< 0.5
< 0.5
Cooling water requirement
—
Determined by actual design of external liquid-to-air or liquid-to-liquid heat exchanger
Power cabling cross sections
6)
• Cable cross-sections, line-side,
max. connectable per phase
with ½” bolt
AWG/MCM
(NEC, CEC)
2 x 1000 MCM
2 x 1000 MCM
2 x 1000 MCM
2 x 1000 MCM
2 x 1000 MCM
mm
2
(DIN VDE)
2 x 500
2 x 500
2 x 500
2 x 500
2 x 500
• Cable cross-sections, motor-side,
max. connectable per phase
with ½” bolt
AWG/MCM
(NEC, CEC)
2 x 1000 MCM
2 x 1000 MCM
2 x 1000 MCM
2 x 1000 MCM
2 x 1000 MCM
mm
2
(DIN VDE)
2 x 500
2 x 500
2 x 500
2 x 500
2 x 500
• PE
7)
connection, max.
connection cross-section at
enclosure with ½” bolt
AWG/MCM
(NEC, CEC)
1000 MCM
1000 MCM
1000 MCM
1000 MCM
1000 MCM
mm
2
(DIN VDE)
500
500
500
500
500
Degree of protection
MV
LV
NEMA 12/ IP54
NEMA 1/IP21
NEMA 12/ IP54
NEMA 1/IP21
NEMA 12/ IP54
NEMA 1/IP21
NEMA 12/ IP54
NEMA 1/IP21
NEMA 12/ IP54
NEMA 1/IP21
Drive dimensions (overall drive dimensions)
• Width
in
mm
474
12040
474
12040
474
12040
474
12040
478
12140
• Height
in
mm
115
2920
115
2920
115
2920
115
2920
125
3180
• Depth
in
mm
70
1780
70
1780
70
1780
70
1780
76
1930
• Dimension drawing
8)
A
A
A
A
A
Drive weight (cell cabinet and transformer cabinet)
• Weight
9)
lb
kg
66231
30042
67630
30677
68973
31286
68973
31286
70266
31873
Type specific technical data
(continued)
Type Specific Technical Data
1)
The Specifications for the typical motor current and the power data in
hp and kW are approximate values only; these have been calculated for
operation with induction motors and for a typical power factor
c
s
and motor efficiency. Both approximate values have to be adapted to
the motor that is actually used.
2)
Values at 100% of rated speed and torque; includes drive and input
transformer.
3)
120/240 V AC for NXGII control and 120 V AC internal heat exchanger
in water-cooled systems.
4)
Includes cooling blowers/pumps; largest unit shown. CPT: Control
power transformer.
5)
Percentage of transformer kVA.
6)
Maximum installable size per phase.
7)
PE - Protective Earth.
8)
For dimension drawings please refer to Section 5, pg 5/11.
9)
Drive Weight is based on cell cabinet, transformer cabinet, and coolant
cabinet only.