SIEMENS
ROBICON Perfect Harmony
Liquid-cooled drives
3
3/5
Siemens D 16.2 – 2012
Type specific technical data
ROBICON Perfect Harmony
liquid-cooled drive version
6SR3252-
0.B44-0..0
6SR3252-
0.B44-5..0
6SR3252-
0.B45-0..0
6SR3252-
0.B45-5..0
6SR3252-
0.B46-0..0
Motor voltage 3.3
Max. output voltage
kV
4
4
4
4
4
Type rating
kVA
3510
3950
4390
4830
5025
Shaft output
1)
hp
4000
4500
5000
5500
5726
kW
2984
3357
3730
4103
4271
Typical motor current
1)
A
614.79
691.64
768.49
845.34
880.00
Power cell current
A
880
880
880
880
880
Number of cells
9
9
9
9
9
Transformer rating
kVA
4000
4500
5000
5500
6000
Power losses of drive system
• Copper transformer
kW
< 140
< 158
< 175
< 193
< 210
Efficiency P
out
/P
in
2)
of drive system
• Copper transformer
%
96.5
96.5
96.5
96.5
96.5
Auxiliary supply
• Single-phase w/o options
3)
kVA
2.5
2.5
2.5
2.5
2.5
• Single-phase w/ all options
3)
kVA
2.5
2.5
2.5
2.5
2.5
• Three-phase w/o CPT
4)
kVA
25
25
25
25
25
• Three-phase w/ CPT and all
-options
4)
kVA
27.5
27.5
27.5
27.5
27.5
System pre-charge
5)
%
< 0.5
< 0.5
< 0.5
< 0.5
< 0.5
Cooling water requirement
–
Determined by actual design of external liquid-to-air or liquid-to-liquid heat exchanger
Power cabling cross sections
6)
• Cable cross-sections, line-side, max.
connectable per phase with ½” bolt
AWG/MCM
(NEC, CEC)
2 x 1000 MCM
2 x 1000 MCM
2 x 1000 MCM
2 x 1000 MCM
2 x 1000 MCM
mm
2
(DIN VDE)
2 x 500
2 x 500
2 x 500
2 x 500
2 x 500
• Cable cross-sections, motor-side,
max. connectable per phase with
½” bolt
AWG/MCM
(NEC, CEC)
2 x 1000 MCM
2 x 1000 MCM
2 x 1000 MCM
2 x 1000 MCM
2 x 1000 MCM
mm
2
(DIN VDE)
2 x 500
2 x 500
2 x 500
2 x 500
2 x 500
• PE
7)
connection, max. connection
cross-section at enclosure with
½” bolt
AWG/MCM
(NEC, CEC)
1000 MCM
1000 MCM
1000 MCM
1000 MCM
1000 MCM
mm
2
(DIN VDE)
500
500
500
500
500
Degree of protection
MV
LV
NEMA 12/ IP54
NEMA 1/IP21
NEMA 12/ IP54
NEMA 1/IP21
NEMA 12/ IP54
NEMA 1/IP21
NEMA 12/ IP54
NEMA 1/IP21
NEMA 12/ IP54
NEMA 1/IP21
Drive dimensions (overall drive dimensions)
• Width
in
mm
370
9400
370
9400
370
9400
370
9400
370
9400
• Height
in
mm
114
2894
114
2894
114
2894
114
2894
114
2894
• Depth
in
mm
66
1680
66
1680
66
1680
66
1680
66
1680
• Dimension drawing
8)
A
A
A
A
A
Drive weight (cell cabinet and transformer cabinet)
• Weight
9)
lb
kg
33566
21837
34672
22339
35719
22814
36716
23266
37670
23699
1)
The Specifications for the typical motor current and the power data in
hp and kW are approximate values only; these have been calculated for
operation with induction motors and for a typical power factor
c
s
and motor efficiency. Both approximate values have to be adapted to
the motor that is actually used.
2)
Values at 100% of rated speed and torque; includes drive and input
transformer.
3)
120/240 V AC for NXGII control and 120 V AC internal heat exchanger
in water-cooled systems.
4)
Includes cooling blowers/pumps; largest unit shown. CPT: Control
power transformer.
5)
Percentage of transformer kVA.
6)
Maximum installable size per phase.
7)
PE - Protective Earth.
8)
For dimension drawings please refer to Section 5, pg 5/11.
9)
Drive Weight is based on cell cabinet, transformer cabinet, and coolant
cabinet only.
Type Specific Technical Data