SIEMENS
ROBICON Perfect Harmony
Liquid-cooled drives
2
2/15
Siemens D 16.2 – 2012
Selection and ordering data (continued)
Motor voltage 6.9/7.2kV
Motor
voltage
Type
rating
Shaft
output
1)
Shaft
output
1)
Typical
motor
current
1)
Power
cell
current
Number of
cells
Transformer
rating
Order number
Generation
kV
kVA
hp
kW
A
A
kVA
7.2
7030
8000
5968
563.56
880
18
8000
6SR3252-3
B48-0
0
WCIII
7.2
7470
8500
6341
598.78
880
18
8500
6SR3252-3
B48-5
0
WCIII
7.2
7910
9000
6714
634.00
880
18
9000
6SR3252-3
B48-7
0
WCIII
7.2
8350
9500
7087
669.22
880
18
9500
6SR3252-3
B48-8
0
WCIII
7.2
8780
10000
7460
704.45
880
18
10000
6SR3252-3
B52-0
0
WCIII
7.2
9660
11000
8206
774.89
880
18
11000
6SR3252-3
B52-2
0
WCIII
7.2
10540
12000
8952
845.34
880
18
12000
6SR3252-3
B52-4
0
WCIII
7.2
10970
12492
9319
880.00
880
18
13000
6SR3252-3
B52-6
0
WCIII
7.2
11420
13000
9698
915.78
1250
18
13000
6SR3252-3
C52-6
0
WCIII
7.2
12300
14000
10444
986.23
1250
18
14000
6SR3252-3
C52-8
0
WCIII
7.2
13180
15000
11190
1056.67
1250
18
15000
6SR3252-3
C53-0
0
WCIII
7.2
14060
16000
11936
1127.12
1250
18
16000
6SR3252-3
C53-2
0
WCIII
7.2
14930
17000
12682
1197.56
1250
18
17000
6SR3252-3
C53-4
0
WCIII
7.2
15585
17744
13237
1250.00
1250
18
18000
6SR3252-3
C53-6
0
WCIII
1)
The specifications for the typical motor current and the power data in hp and kW are approximate values only; these have been calculated for
operation with induction motors and for typical power factor co-efficiency. Both approximate values have to be adapted to the motor that is
actually used.
Selection and Ordering Data
For Order Number Supplements, see pages
2-15 to 2-18