SIEMENS
3/20
Siemens D 83.1 · 2016
3
Motors without Explosion Protection
LOHER CHEMSTAR and VARIO 1PS0 motor series
Motors with Premium Efficiency IE3 in cast-iron and steel versions
■
Selection and ordering data
(continued)
Operating values at rated power
Motor type
Article No.
P
rated,
60 Hz
Frame
size
n
rated,
60 Hz
T
rated,
60 Hz
IE
class
rated.
60 Hz,
4/4
rated.
60 Hz,
3/4
rated.
60 Hz,
2/4
cos
rat.,
60 Hz,
4/4
I
rated,
60 Hz,
460 V
T
LR
/
T
rated
I
LR
/
I
rated
T
B/
T
rated
m
IM B3
J
kW
FS
rpm
Nm
–
%
%
%
–
A
–
–
–
kg
kgm
2
•
Cooling: self-ventilated (IC 411)
•
Efficiency: Premium Efficiency IE3 in accordance with IEC 60034-30-1
•
Insulation: Thermal class 155 (temperature class F), IP55 degree of protection, utilization in accordance with thermal class 130
(temperature class B), S1-100 %
2-pole: 3600 rpm at 60 Hz
LOHER CHEMSTAR
0.43
71 B
3445
1.19
IE3
79.5
79.1
75.5
0.76
0.89
1.19
6.0
3.6
ANGA-071BS-02
1PS0070-
■
BD
■
■
-0AH4
27
0.0005
0.63
71 B
3460
1.74
IE3
81.5
80.6
76.0
0.76
1.28
1.74
6.6
3.9
ANGA-071BT-02
1PS0071-
■
BD
■
■
-0AH4
28
0.0006
0.86
80 B
3450
2.38
IE3
83.8
84.6
83.5
0.86
1.50
2.38
6.4
3.1
ANGA-080BS-02
1PS0080-
■
BD
■
■
-0AH4
29
0.0011
1.27
80 B
3480
3.48
IE3
85.5
85.8
84.0
0.85
2.20
3.48
7.4
3.4
ANGA-080BT-02
1PS0081-
■
BD
■
■
-0AH4
30
0.0013
1.75
90 L
3510
4.76
IE3
85.5
85.6
84.0
0.87
2.95
4.76
8.7
4.2
ANGA-090LS-02
1PS0095-
■
BD
■
■
-0AH4
36
0.0021
2.55
90 L
3510
6.90
IE3
86.7
87.1
85.9
0.88
4.20
6.90
8.3
4.2
ANGA-090LT-02
1PS0098-
■
BD
■
■
-0AH4
40
0.0031
3.45
100 L
3525
9.30
IE3
88.6
89.2
88.5
0.89
5.50
9.30
8.5
4.7
ANGA-100LT-02
1PS0106-
■
BD
■
■
-0AH4
56
0.0054
4.55
112 M
3555
12.2
IE3
90.0
90.0
88.7
0.90
7.10
12.2
9.0
4.1
ANGA-112MT-02
1PS0113-
■
BD
■
■
-0AH4
66
0.012
6.3
132 S
3545
17.0
IE3
90.5
91.0
90.2
0.91
9.60
17.0
7.5
3.8
ANGA-132SS-02
1PS0131-
■
BD
■
■
-0AH4
95
0.024
8.6
132 S
3555
23.1
IE3
91.8
92.4
92.1
0.92
12.8
23.1
8.4
4.1
ANGA-132ST-02
1PS0132-
■
BD
■
■
-0AH4
105
0.031
12.6
160 M
3555
33.8
IE3
91.5
90.8
89.3
0.89
19.4
33.8
7.6
3.7
ANGA-160MS-02
1PS0163-
■
BD
■
■
-0AH4
174
0.053
17.3
160 M
3560
46.4
IE3
92.0
92.0
90.6
0.88
27.0
46.4
8.7
4.2
ANGA-160MT-02
1PS0165-
■
BD
■
■
-0AH4
184
0.061
21.3
160 L
3560
57.1
IE3
92.5
92.4
91.1
0.91
32.0
57.1
8.2
3.8
ANGA-160LT-02
1PS0166-
■
BD
■
■
-0AH4
195
0.068
24.5
180 M
3555
65.8
IE3
93.9
94.2
93.6
0.89
37.0
65.8
7.5
3.6
ANGA-180MT-02
1PS0183-
■
BD
■
■
-0AH4
241
0.08
33.5
200 L
3555
90.0
IE3
94.2
94.4
94.0
0.87
51.0
90.0
7.1
3.3
ANGA-200LS-02
1PS0206-
■
BD
■
■
-0AH4
317
0.13
41.5
200 L
3555
111.5
IE3
94.2
94.0
92.9
0.89
62.0
111.5 7.1
3.2
ANGA-200LT-02
1PS0208-
■
BD
■
■
-0AH4
340
0.158
51
225 M
3560
136.8
IE3
94.5
95.0
94.5
0.89
76.0
136.8 6.8
3.2
ANGA-225MT-02
1PS0223-
■
BD
■
■
-0AH4
435
0.26
62
250 M
3575
165.6
IE3
93.6
93.6
92.7
0.90
92.0
165.6 6.7
3.0
ANGA-250MN-02
1PS0253-
■
BD
■
■
-0AH4
505
0.46
75
280 S
3578
200
IE3
94.1
93.9
92.7
0.89
112
200
7.6
3.2
ANGA-280SM-02
1PS0280-
■
BD
■
■
-0AH4
665
0.77
90
280 M
3578
240
IE3
95.0
94.9
93.9
0.90
132
240
8.1
3.3
ANGA-280MN-02
1PS0283-
■
BD
■
■
-0AH4
720
0.94
123
315 S
3582
328
IE3
95.0
95.0
94.2
0.91
179
328
7.2
3.0
ANGA-315SL-02
1PS0311-
■
BD
■
■
-0AH4
955
1.39
148
315 M
3582
395
IE3
95.4
95.3
94.6
0.91
215
395
7.1
3.0
ANGA-315ML-02
1PS0313-
■
BD
■
■
-0AH4
1025 1.6
160
315 M
3587
426
IE3
95.4
95.1
94.0
0.91
230
426
7.8
3.4
ANGA-315MN-02
1PS0315-
■
BD
■
■
-0AH4
1105 1.9
224
315 L
3582
597
IE3
95.8
95.9
95.4
0.92
320
597
7.1
2.9
ANGA-315LL-02
1PS0316-
■
BD
■
■
-0AH4
1355 2.3
270
315 L
3582
720
IE3
96.0
96.0
95.5
0.92
385
720
9.5
3.7
ANGA-315LN-02
1PS0318-
■
BD
■
■
-0AH4
1505 2.5
Operating modes
Frame size
Order code
Line operation
71 … 315
0
–
Converter operation, standard insulation
71 … 315
1
–
Voltages
Frame size
Order code
For other voltages,
see Page 3/27
71 … 315
9
…
Types of construction
Frame size
Order code
IM B3
71 … 315
0
–
IM B5
71 … 315
1
–
IM B34
71 … 112
2
–
IM B14
71 … 112
3
–
IM V1/cover
71 … 315
4
–
IM B35
71 … 315
6
–
For other types of construction,
see from Page 1/29 and 3/28
71 … 315
9
…
© Siemens AG 2016