(continued)
Operating values at rated power
Motor type
Article No.
P
rat.,
50 Hz
Frame
size
n
rated,
50 Hz
T
rated
,
50 Hz
IE
class
rated,
50 Hz,
4/4
rated,
50 Hz,
3/4
rated,
50 Hz,
2/4
cos
rat.,
50 Hz,
4/4
I
rated,
50 Hz,
400 V
I
rated,
50 Hz,
500 V
I
rated,
50 Hz,
690 V
T
LR
/
T
rat.
I
LR
/
I
rat.
T
B
/
T
rat.
m
IM B3
J
kW
FS
rpm
Nm
–
%
%
%
–
A
A
A
–
–
–
kg
kgm
2
•
Cooling: self-ventilated (IC 411)
•
Efficiency: Premium Efficiency IE3 according to IEC 60034-30-1
•
Insulation: thermal class 155 (temperature class F), IP55 degree of protection,
utilization in accordance with thermal class 130 (temperature class B), S1-100 %
•
Type of protection: "Non sparking" in accordance with EN 60079-15; 2010: II 3G Ex nA IIC T3 Gc
4-pole: 1500 rpm at 50 Hz
LOHER CHEMSTAR
0.25
71 B
1395 1.71
IE3
73.5 73.7 70.4 0.72
0.68 0.55 0.40 2.5
4.2
2.6
ANGK-071BS-04
1PS1070-
■
BD
■
■
-3BH4
27
0.0010
0.37
71 B
1410 2.51
IE3
77.3 76.8 73.2 0.70
0.99 0.79 0.57 3.1
4.8
3.1
ANGK-071BT-04
1PS1071-
■
BD
■
■
-3BH4
29
0.0014
0.55
80 B
1440 3.65
IE3
80.8 81.1 79.3 0.78
1.26 1.01 0.73 2.1
5.9
3.1
ANGK-080BS-04
1PS1080-
■
BD
■
■
-3BH4
29
0.0017
0.75
80 B
1450 4.94
IE3
83.9 83.5 81.5 0.75
1.72 1.38 1.00 2.7
7.1
3.9
ANGK-080BT-04
1PS1081-
■
BD
■
■
-3BH4
32
0.0029
1.1
90 L
1440 7.30
IE3
84.5 85.0 83.6 0.78
2.40 1.93 1.40 2.9
6.9
3.6
ANGK-090LS-04
1PS1095-
■
BD
■
■
-3BH4
35
0.0036
1.5
90 L
1445 9.90
IE3
85.8 86.4 85.2 0.80
3.15 2.50 1.83 2.7
7.2
3.6
ANGK-090LT-04
1PS1098-
■
BD
■
■
-3BH4
39
0.0049
2.2
100 L
1465 14.3
IE3
88.4 88.5 87.8 0.83
4.35 3.45 2.50 3.2
8.3
4.4
ANGK-100LS-04
1PS1106-
■
BD
■
■
-3BH4
61
0.014
3
100 L
1460 19.6
IE3
88.9 89.2 88.2 0.83
5.90 4.70 3.40 2.5
8.3
3.9
ANGK-100LT-04
1PS1108-
■
BD
■
■
-3BH4
61
0.014
4
112 M
1460 26.2
IE3
89.5 90.2 89.7 0.82
7.90 6.30 4.55 2.4
7.1
3.7
ANGK-112MT-04
1PS1113-
■
BD
■
■
-3BH4
67
0.017
5.5
132 S
1470 35.7
IE3
90.2 90.5 90.0 0.82
10.7 8.60 6.20 2.9
8.6
3.7
ANGK-132ST-04
1PS1131-
■
BD
■
■
-3BH4
106
0.046
7.5
132 M
1470 48.7
IE3
91.1 91.7 91.4 0.85
14.0 11.2 8.10 2.6
8.2
3.7
ANGK-132MT-04
1PS1133-
■
BD
■
■
-3BH4
111
0.046
11
160 M
1475 71.2
IE3
92.0 92.3 91.7 0.84
20.5 16.4 11.9 2.6
7.6
3.4
ANGK-160MS-04
1PS1163-
■
BD
■
■
-3BH4
176
0.083
15
160 L
1480 96.8
IE3
92.5 92.7 92.1 0.82
28.5 23.0 16.5 2.5
8.5
3.8
ANGK-160LT-04
1PS1166-
■
BD
■
■
-3BH4
195
0.099
18.5
180 M
1470 120.2 IE3
92.6 93.1 93.0 0.82
35.0 28.0 20.5 2.5
7.2
3.3
ANGK-180MS-04
1PS1183-
■
BD
■
■
-3BH4
241
0.13
22
180 L
1470 142.9 IE3
93.0 93.6 93.6 0.83
41.0 33.0 24.0 2.3
6.8
3.3
ANGK-180LT-04
1PS1186-
■
BD
■
■
-3BH4
251
0.14
30
200 L
1470 194.9 IE3
93.9 94.6 94.7 0.84
55.0 44.0 32.0 2.6
7.3
3.1
ANGK-200LT-04
1PS1206-
■
BD
■
■
-3BH4
337
0.22
37
225 S
1478 239
IE3
93.9 94.5 94.4 0.86
66.0 53.0 38.5 2.5
6.4
2.7
ANGK-225SS-04
1PS1220-
■
BD
■
■
-3BH4
418
0.42
45
225 M
1478 291
IE3
94.2 94.9 95.1 0.86
80.0 64.0 46.5 2.6
6.4
2.7
ANGK-225MT-04
1PS1223-
■
BD
■
■
-3BH4
440
0.47
55
250 M
1482 354
IE3
94.8 95.3 95.2 0.87
96.0 77.0 56.0 2.5
6.8
2.9
ANGK-250MN-04
1PS1253-
■
BD
■
■
-3BH4
540
0.85
75
280 S
1485 482
IE3
95.1 95.3 95.0 0.86
132
106
77.0 2.5
6.9
3.0
ANGK-280SM-04
1PS1280-
■
BD
■
■
-3BH4
710
1.39
90
280 M
1485 579
IE3
95.3 95.5 95.3 0.87
157
125
91.0 2.6
7.2
3.0
ANGK-280MN-04
1PS1283-
■
BD
■
■
-3BH4
785
1.7
110
315 S
1488 706
IE3
95.5 95.8 95.5 0.87
191
153
111
2.6
6.8
2.9
ANGK-315SL-04
1PS1311-
■
BD
■
■
-3BH4
965
2.2
132
315 M
1490 846
IE3
95.6 95.9 95.9 0.87
230
183
133
2.8
7.3
3.0
ANGK-315ML-04
1PS1313-
■
BD
■
■
-3BH4
1045 2.9
160
315 M
1490 1025
IE3
95.8 96.1 96.1 0.87
275
220
161
2.9
7.3
3.1
ANGK-315MN-04
1PS1315-
■
BD
■
■
-3BH4
1075 3.1
200
315 L
1488 1284
IE3
96.0 96.3 96.1 0.88
340
275
198
3.2
7.4
3.0
ANGK-315LL-04
1PS1316-
■
BD
■
■
-3BH4
1295 3.7
250
315 L
1492 1600
IE3
96.1 96.2 95.8 0.86
435
350
255
2.5
7.5
3.0
ANGK-315LM-04
1PS1317-
■
BD
■
■
-3BH4
1500 4.2
Operating modes
Frame size
Order code
Line operation
71 ... 315
0
–
Converter operation, standard insulation
1)
71 ... 315
1
–
Voltages
Frame size
Order code
230 V/400 V, 50 Hz
71 ... 280
1
–
500 VY, 50 Hz
71 ... 315
2)
3
–
400 V/690 V, 50 Hz
71 ... 315
6
–
690 VY, 50 Hz
71 ... 315
8
–
For other voltages,
see Page 2/110
71 ... 315
9
…
Types of construction
Frame size
Order code
IM B3
71 ... 315
0
–
IM B5
71 ... 315
1
–
IM B34
71 ... 112
2
–
IM B14
71 ... 112
3
–
IM V1/cover
71 ... 315
4
–
IM B35
71 ... 315
6
–
For other types of construction,
see from Page 1/29 and 2/111
71 ... 315
9
…
1)
Can only be ordered with additional identification code
-Z
and order code
M73
.
2)
Up to 200 kW.
© Siemens AG 2016