SIEMENS
2/59
Siemens D 83.1 · 2016
2
Motors with Explosion Protection
LOHER CHEMSTAR and VARIO 1PS4 and 1PS5 motor series
Motors with Premium Efficiency IE3 in cast-iron and steel versions
■
Selection and ordering data
(continued)
Operating values at rated power
Motor type
Article No.
P
rated,
60 Hz
Frame
size
n
rated,
60 Hz
T
rated,
60 Hz
IE
class
rated,
60 Hz,
4/4
rated,
60 Hz,
3/4
rated,
60 Hz,
2/4
cos
rat.,
60 Hz,
4/4
I
rated
,
60 Hz,
460 V
T
LR
/
T
rat.
I
LR
/
I
rat.
T
B
/
T
rat.
m
IM B3
J
kW
FS
rpm
Nm
–
%
%
%
–
A
–
–
–
kg
kgm
2
•
Cooling: self-ventilated (IC 411)
•
Efficiency: Premium Efficiency IE3 according to IEC 60034-30-1
•
Insulation: thermal class 155 (temperature class F), IP55 degree of protection,
utilization in accordance with thermal class 130 (temperature class B), S1-100 %
•
Type of protection: "Explosion-proof enclosure" according to EN 60079-1; 2007: II 2G Ex d(e) IIC T4 Gb
4-pole: 1800 rpm at 60 Hz
LOHER CHEMSTAR
0.29
71 B
1695
1.63
IE3
75.0
75.5
72.0
0.72
0.67
2.5 2.6
DNG
W
-071BS-04
1PS
5
070-
■
BD
■
■
-4BH4
27
0.0010
0.43
71 B
1710
2.40
IE3
80.2
79.5
76.1
0.70
0.96
3.0 3.1
DNG
W
-071BT-04
1PS
5
071-
■
BD
■
■
-4BH4
29
0.0014
0.55
80 B
1740
3.02
IE3
81.1
81.3
79.4
0.78
1.09
2.4 3.3
DNG
W
-080BS-04
1PS
5
080-
■
BD
■
■
-4BH4
29
0.0017
0.75
80 B
1760
4.07
IE3
85.5
84.5
81.0
0.71
1.55
3.1 4.7
DNG
W
-080BT-04
1PS
5
081-
■
BD
■
■
-4BH4
32
0.0029
1.27
90 L
1740
7.00
IE3
86.5
86.9
85.6
0.79
2.35
2.9 3.8
DNG
W
-090LS-04
1PS
5
095-
■
BD
■
■
-4BH4
35
0.0036
1.75
90 L
1740
9.60
IE3
87.0
87.4
86.1
0.8
3.15
2.6 3.7
DNG
W
-090LT-04
1PS
5
098-
■
BD
■
■
-4BH4
39
0.0049
2.55
100 L
1765
13.8
IE3
89.5
89.7
88.5
0.84
4.25
3.0 4.4
DNG
W
-100LS-04
1PS
5
106-
■
BD
■
■
-4BH4
61
0.014
3.45
100 L
1760
18.7
IE3
89.8
90.1
89.5
0.84
5.70
2.7 3.9
DNG
W
-100LT-04
1PS
5
108-
■
BD
■
■
-4BH4
61
0.014
4.55
112 M
1760
24.7
IE3
90.5
91.0
90.5
0.83
7.60
2.5 3.8
DNG
W
-112MT-04
1PS
5
113-
■
BD
■
■
-4BH4
69
0.017
6.30
132 S
1770
34.0
IE3
91.7
92.0
91.3
0.83
10.4
3.4 3.8
DNG
W
-132ST-04
1PS
5
131-
■
BD
■
■
-4BH4
108
0.046
8.60
132 M
1770
46.4
IE3
91.7
92.2
91.8
0.86
13.7
2.3 3.6
DNG
W
-132MT-04
1PS
5
133-
■
BD
■
■
-4BH4
113
0.046
12.6
160 M
1770
68.0
IE3
92.4
92.6
92.0
0.85
20.0
2.6 3.3
DNG
W
-160MS-04
1PS
5
163-
■
BD
■
■
-4BH4
178
0.083
17.3
160 L
1775
93.1
IE3
93.6
93.7
92.9
0.83
28.0
2.5 3.7
DNG
W
-160LT-04
1PS
5
166-
■
BD
■
■
-4BH4
197
0.099
21.3
180 M
1770
114.9
IE3
93.6
94.0
93.8
0.83
34.5
2.4 3.2
DNG
W
-180MS-04
1PS
5
183-
■
BD
■
■
-4BH4
244
0.13
25.3
180 L
1770
136.5
IE3
93.6
94.1
94.0
0.83
41.0
2.2 3.2
DNG
W
-180LT-04
1PS
5
186-
■
BD
■
■
-4BH4
254
0.14
30
200 L
1778
161.1
IE3
94.3
94.5
93.9
0.84
47.5
3.0 3.5
DNG
W
-200LT-04
1PS
5
206-
■
BD
■
■
-4BH4
340
0.22
37
225 S
1782
198.3
IE3
94.6
94.7
94.2
0.85
58.0
2.8 3.0
DNG
W
-225SS-04
1PS
5
220-
■
BD
■
■
-4BH4
421
0.42
45
225 M
1782
241
IE3
95.0
95.0
94.5
0.84
71.0
2.9 3.0
DNG
W
-225MT-04
1PS
5
223-
■
BD
■
■
-4BH4
443
0.47
55
250 M
1786
294
IE3
95.4
95.6
95.1
0.86
84.0
2.8 3.2
DNG
W
-250MN-04
1PS
5
253-
■
BD
■
■
-4BH4
570
0.85
75
280 S
1788
401
IE3
95.5
95.3
94.5
0.85
116
2.8 3.3
DNG
W
-280SM-04
1PS
5
280-
■
BD
■
■
-4BH4
755
1.39
90
280 M
1788
481
IE3
95.5
95.5
94.9
0.87
136
2.9 3.3
DNG
W
-280MN-04
1PS
5
283-
■
BD
■
■
-4BH4
820
1.7
127
315 S
1788
678
IE3
95.8
96.1
95.8
0.87
191
2.5 2.7
DNG
W
-315SL-04
1PS
5
311-
■
BD
■
■
-4BH4
1010 2.2
152
315 M
1788
812
IE3
96.2
96.5
96.3
0.88
225
2.7 2.8
DNG
W
-315ML-04
1PS
5
313-
■
BD
■
■
-4BH4
1090 2.9
184
315 M
1788
983
IE3
96.2
96.5
96.3
0.88
275
3.0 2.9
DNG
W
-315MN-04
1PS
5
315-
■
BD
■
■
-4BH4
1120 3.1
185
315 L
1791
986
IE3
96.2
96.2
95.5
0.87
275
3.9 3.6
DNG
W
-315LL-04
1PS
5
316-
■
BD
■
■
-4BH4
1340 3.7
250
315 L
1791
1333
IE3
96.2
96.0
95.3
0.85
385
3.8 3.8
DNG
W
-315LM-04
1PS
5
317-
■
BD
■
■
-4BH4
1550 4.2
490
355 M
1789
2616
IE3
96.2
96.0
95.3
0.86
740
2.3 2.4
DNG
W
-355MT-04
1)
1PS
5
357-
■
BD
■
■
-4BH4
2750 8.5
Operating modes
Frame size
Order code
Line operation
71 ... 355
0
–
Converter operation, standard insulation
71 ... 355
1
–
Voltages
Frame size
Order code
For other voltages,
see Page 2/65
71 ... 355
9
…
Types of construction
Frame size
Order code
IM B3
71 ... 355
0
–
IM B5
71 ... 315
1
–
IM B34
71 ... 112
2
–
IM B14
71 ... 112
3
–
IM V1/cover
71 ... 355
4
–
IM B35
71 ... 355
6
–
For other types of construction,
see from Page 1/29 and 2/66
71 ... 355
9
…
1)
Direction of rotation must be specified (option
K97
or
K98
).
© Siemens AG 2016