SIEMENS
1/94
Siemens D 83.1 · 2016
1
Introduction
General technical specifications
Converter operation – VSD drive configuration
■
Overview
(continued)
Type
Motor type
Line
operation
Operating values for converter operation – rated data for rating plate
Setting range 1 : 10
P
VSD
= constant
1)
T
~
n
2
Any load characteristic
Constant flux
Field weakening
5 ... 50 Hz
50 Hz ...
f
max
Rated power
Power
Torque
Speed
Current
Max.
frequency
Power
Current
(values at 400 V, 50 Hz)
(at 400 V
f
max
)
P
rated
P
VSD
T
VSD
n
asyn_VSD
I
VSD
f
max
P
VSD
I
VSD
kW
kW
Nm
rpm
A
Hz
kW
A
Cooling: self-ventilated (IC411)
Efficiency: High Efficiency IE2
Ambient temperature: 40 °C, installation altitude: 1000 m
6-pole: 1000 rpm at 50 Hz
Insulation: Thermal class 155 (F) – VSD utilization of the winding in accordance with thermal class 155 (F)
– can be ordered with additional
1PS
070-1BD..-.CA4
-071BS-06.
0.25
0.30
3.45
837
0.82
61
0.30
0.81
1PS
080-1BD
....
CA4
-080BR-06.
0.37
0.45
4.80
906
1.18
73
0.45
1.16
1PS
081-1BD..-.CA4
-080BS-06.
0.55
0.65
7.10
912
1.75
88
0.65
1.69
1PS
095-1BD..-.CA4
-090LR-06.
0.75
0.90
9.60
918
2.35
76
0.90
2.25
1PS
098-1BD..-.CA4
-090LS-06.
1.10
1.30
14.1
918
3.30
79
1.30
3.15
1PS
106-1BD..-.CA4
-100LS-06.
1.50
1.80
18.5
962
4.15
85
1.80
4.00
1PS
113-1BD..-.CA4
-112MS-06.
2.20
2.70
27.3
956
5.90
85
2.70
5.80
1PS
131-1BD..-.CA4
-132SR-06.
3.00
3.50
35.0
964
7.80
81
3.50
7.70
1PS
133-1BD..-.CA4
-132MR-06.
4.00
4.20
42.2
968
9.50
82
4.20
9.30
1PS
135-1BD..-.CA4
-132MS-06.
5.50
5.80
58.1
968
12.6
93
5.80
12.4
1PS
163-1BD..-.CA4
-160MR-06.
7.50
8.80
87.0
970
18.8
71
8.80
18.7
1PS
166-1BD..-.CA4
-160LS-06.
11.0
11.7
115.6
973
25.0
78
11.7
24.5
1PS
186-1BD..-.CA4
-180LS-06.
15.0
16.0
157.6
973
32.5
100
16.0
32.5
1PS
206-1BD..-.CA4
-200LR-06.
18.5
19.8
193.8
976
38.0
93
19.8
38.0
1PS
208-1BD..-.CA4
-200LS-06.
22.0
22.6
221
977
43.5
97
22.6
43.5
1PS
223-1BD..-.CA4
-225MS-06.
30.0
32.1
314
979
60.0
87
32.1
60.0
1PS
253-1BD..-.CA4
-250MM-06.
37.0
38.0
371
981
72.0
80
38.0
71.0
1PS
280-1BD..-.CA4
-280SL-06.
45.0
48.2
468
984
88.0
75
48.2
88.0
1PS
283-1BD..-.CA4
-280MM-06.
55.0
56.6
549
985
102
75
56.6
102
1PS
311-1BD..-.CA4
-315SL-06.
75.0
83.5
812
987
152
65
83.5
151
1PS
313-1BD..-.CA4
-315ML-06.
90.0
100.5
974
987
182
65
100.5
182
1PS
314-1BD..-.CA4
-315MM-06.
110
129.5
1259
986
230
65
129.5
225
1PS
315-1BD..-.CA4
-315MN-06.
132
147.5
1428
987
260
65
147.5
260
1PS
316-1BD..-.CA4
-315LL-06.
160
164.5
1593
988
290
65
164.5
290
1PS
317-1BD..-.CA4
-315LM-06.
200
185.5
1788
991
345
65
185.5
345
1PS
0
356-1BD..-0CB2
A N G A
-355LB-06.
250
230
2227
994
425
60
230
425
1PS
1
317-1BD..-3CB2
A N G K
-355LB-06.
315
230
2227
994
425
60
230
425
1PS
5
353-1BD..-4CA3
D N G W
-355MR-06.
315
259
2496
994
485
60
259
480
1PS
5
355-1BD..-4CA3
D N G W
-355MS-06.
315
292
2808
994
540
60
292
540
1PS
5
357-1BD..-4CA3
D N G W
-355MT-06.
360
333
3206
994
610
60
333
610
Motor
0
A N G A
LOHER CHEMSTAR 1PS0
1
A N G K
LOHER CHEMSTAR 1PS1 (converter operation Ex nA can only be ordered with add. identification code
-Z
and order code
M73
)
5
D N G W
LOHER CHEMSTAR 1PS5
1)
The reduced torque in the field-weakening range shall be calculated
as follows:
T
[Nm] = 9550 ·
P
VSD
[kW]/
n
[rpm]
© Siemens AG 2016