SIEMENS
1/92
Siemens D 83.1 · 2016
1
Introduction
General technical specifications
Converter operation – VSD drive configuration
■
Overview
(continued)
Type
Motor type
Line
operation
Operating values for converter operation – rated data for rating plate
Setting range 1 : 10
P
VSD
= constant
1)
T
~
n
2
Any load characteristic
Constant flux
Field weakening
5 ... 50 Hz
50 Hz ...
f
max
Rated power
Power
Torque
Speed
Current
Max.
frequency
Power
Current
(values at 400 V, 50 Hz)
(at 400 V
f
max
)
P
rated
P
VSD
T
VSD
n
asyn_VSD
I
VSD
f
max
P
VSD
I
VSD
kW
kW
Nm
rpm
A
Hz
kW
A
Cooling: self-ventilated (IC411)
Efficiency: High Efficiency IE2
Ambient temperature: 40 °C, installation altitude: 1000 m
6-pole: 1000 rpm at 50 Hz
Insulation: Thermal class 155 (F) – VSD utilization of the winding in accordance with thermal class 130 (B)
1PS
070-1BD..-.CA4
-071BS-06.
0.25
0.27
3.10
853
0.80
67
0.27
0.79
1PS
080-1BD
....
CA4
-080BR-06.
0.37
0.41
4.32
915
1.12
81
0.41
1.11
1PS
081-1BD..-.CA4
-080BS-06.
0.55
0.60
6.40
921
1.66
97
0.60
1.63
1PS
095-1BD..-.CA4
-090LR-06.
0.75
0.80
8.70
927
2.20
85
0.80
2.10
1PS
098-1BD..-.CA4
-090LS-06.
1.10
1.20
12.7
927
3.10
88
1.20
3.00
1PS
106-1BD..-.CA4
-100LS-06.
1.50
1.60
16.7
966
3.85
95
1.60
3.70
1PS
113-1BD..-.CA4
-112MS-06.
2.20
2.40
24.6
960
5.50
95
2.40
5.30
1PS
131-1BD..-.CA4
-132SR-06.
3.00
3.10
31.5
968
7.30
90
3.10
7.20
1PS
133-1BD..-.CA4
-132MR-06.
4.00
3.80
38.0
971
8.80
91
3.80
8.70
1PS
135-1BD..-.CA4
-132MS-06.
5.50
5.30
52.3
971
11.7
100
5.30
11.7
1PS
163-1BD..-.CA4
-160MR-06.
7.50
7.90
78.3
973
17.4
79
7.90
17.3
1PS
166-1BD..-.CA4
-160LS-06.
11.0
10.6
104
976
23.0
87
10.6
23.0
1PS
186-1BD..-.CA4
-180LS-06.
15.0
14.4
141.9
976
30.0
100
14.4
30.0
1PS
206-1BD..-.CA4
-200LR-06.
18.5
17.8
174.4
979
35.0
100
17.8
35.0
1PS
208-1BD..-.CA4
-200LS-06.
22.0
20.4
199.1
980
40.0
100
20.4
40.0
1PS
223-1BD..-.CA4
-225MS-06.
30.0
28.9
282
981
55.0
87
28.9
55.0
1PS
253-1BD..-.CA4
-250MM-06.
37.0
34.3
334
983
65.0
80
34.3
65.0
1PS
280-1BD..-.CA4
-280SL-06.
45.0
43.4
421
986
80.0
75
43.4
80.0
1PS
283-1BD..-.CA4
-280MM-06.
55.0
51.0
494
986
93.0
75
51.0
93.0
1PS
311-1BD..-.CA4
-315SL-06.
75.0
75.5
730
988
138
65
75.5
138
1PS
313-1BD..-.CA4
-315ML-06.
90.0
90.5
876
988
166
65
90.5
165
1PS
314-1BD..-.CA4
-315MM-06.
110
117
1133
987
205
65
117
205
1PS
315-1BD..-.CA4
-315MN-06.
132
132.5
1286
988
235
65
132.5
235
1PS
316-1BD..-.CA4
-315LL-06.
160
148
1434
989
265
65
148
265
1PS
317-1BD..-.CA4
-315LM-06.
200
185.5
1788
991
345
65
185.5
345
1PS
0
356-1BD..-0CB2
A N G A
-355LB-06.
250
230
2227
994
425
60
230
425
1PS
1
317-1BD..-3CB2
A N G K
-355LB-06.
315
230
2227
994
425
60
230
425
1PS
5
353-1BD..-4CA3
D N G W
-355MR-06.
315
259
2496
994
485
60
259
480
1PS
5
355-1BD..-4CA3
D N G W
-355MS-06.
315
292
2808
994
540
60
292
540
1PS
5
357-1BD..-4CA3
D N G W
-355MT-06.
360
333
3206
994
610
60
333
610
Motor
0
A N G A
LOHER CHEMSTAR 1PS0
1
A N G K
LOHER CHEMSTAR 1PS1 (converter operation Ex nA can only be ordered with add. identification code
-Z
and order code
M73
)
5
D N G W
LOHER CHEMSTAR 1PS5
1)
The reduced torque in the field-weakening range shall be calculated
as follows:
T
[Nm] = 9550 ·
P
VSD
[kW]/
n
[rpm]