SIEMENS
13/16
Siemens IC 10 · 2017
SIRIUS ACT Pushbuttons and Indicator Lights
General data
13
Type
3SU1.5.-2A
3SU1.5.-2B
3SU1.5.-2C
3SU1.5.-2D
3SU1.5.-2E
3SU1.0.-2A
3SU1.0.-2B
3SU1.0.-2C
3SU1.3.-2A
3SU1.3.-2B
3SU1.3.-2C
3SU1.0.-3E
3SU1.3.-3E
3SU1.5.-3E
3SU1.0.-4B
3SU1.0.-4C
3SU1.0.-4D
3SU1.0.-4F
3SU1.0.-4G
3SU1.0.-4H
3SU1.0.-4J
3SU1.0.-4L
3SU1.0.-5B
3SU1.0.-5H
3SU1.0.-5P
3SU1.0.-5Q
3SU1.0.-5R
3SU1.0.-5S
3SU1.0.-5T
3SU1.0.-5X
3SU1...-4B
3SU1...-4C
3SU1...-4D
3SU1...-4F
3SU1...-4G
3SU1...-4H
3SU1...-4J
3SU1...-4L
3SU1...-5B
3SU1...-5H
3SU1...-5K
3SU1...-5L
3SU1...-5P
3SU1...-5Q
3SU1...-5R
3SU1...-5S
3SU1...-5T
3SU1...-5X
3SU1.0.-7A
3SU1.0.-7B
3SU1.3.-7A
3SU1.3.-7B
3SU1.5.-7A
3SU1.5.-7B
Product version
Selector switches
Toggle switches
Key-operated switches
Coordinate
switches
Mechanical endurance (operating cycles)
300 000
1 000 000
300 000
250 000
Switching frequency
maximum
1/h
1 800
3 600
Shock resistance
acc. to IEC 60068-2-27
Half-sine wave 50
g
/ 11 ms
Vibration resistance
acc. to
IEC 60068-2-6
10 ... 500 Hz: 5
g
IP degree of protection
IP66, IP67, IP69 (IP69K)
IP66, IP67, IP69K
IP66, IP67, IP69 (IP69K)
IP65, IP67
Ambient temperature
• During operation
°C
-25 … +70
• During storage
°C
-40 … +80
Type
3SU1400-
.AA10-1A.0
3SU1400-
1AA10-1GA0,
3SU1400-
1AA10-1RA0
3SU1400-
1AA10-1HA0
3SU1400-
.AA10-3A.0
3SU1400-
1AA10-3HA0
3SU1400-
3AA10-5A.0
Product version
Contact modules
Rated insulation
voltage
V
500
Pollution degree
3
Impulse withstand voltage
Rated value
kV
6
Operational
voltage type
AC/DC
Operational voltage, rated value
• At AC at 50 Hz
V
5 … 500
• At DC
V
5 … 500
Thermal current
A
10
Operational current, rated value
• At AC-12
-
At 24 V
A
10
-
At 230 V
A
8
• At AC-15
-
At 24 V
A
6
-
At 230 V
A
6
4
6
-
At 400 V
A
3
-
At 500 V
A
1.4
• At DC-12
-
At 24 V
A
10
-
At 48 V
A
5
-
At 110 V
A
2.5
-
At 230 V
A
1
0.3
1
0.3
1
-
At 400 V
A
0.3
-
At 500 V
A
0.3
0.2
0.3
• At DC-13
-
At 24 V
A
3
-
At 48 V
A
1.5
-
At 110 V
A
0.7
0.6
0.7
0.6
0.7
-
At 230 V
A
0.3
-
At 400 V
A
0.1
-
At 500 V
A
0.1
Contact reliability
One contact failure per 100 million switching operations (17 V, 5 mA),
one contact failure per 10 million switching operations (5 V, 1 mA)
Mechanical endurance (operating cycles)
typical
10 000 000
Switching frequency
maximum
1/s
3600
Fuse link version required for
short-circuit
protection of
the auxiliary switch with
type of
coordination 1
gG / Dz 10 A, quick-response / Dz 10 A
© Siemens AG 2016