SIMOCODE 3UF Motor Management and Control Devices
SIMOCODE pro 3UF7 Motor Management and Control Devices
General data
10
✓
Detection possible
--
Detection not possible
Current measuring modules or current/voltage measuring
modules
Type
3UF71.0
3UF71.1
3UF71.2
3UF71.3
3UF71.4
Main circuit
Set current
I
e
A
0.3 ... 3
2.4 ... 25
10 ... 100
20 ... 200
63 ... 630
Rated insulation voltage
U
i
V
690; 3UF7103 and 3UF7104: 1 000 (at pollution degree 3)
Rated operational voltage
U
e
V
690
Rated impulse withstand voltage
U
imp
kV
6; 3UF7103 and 3UF7104: 8
Rated frequency
Hz
50/60
Type of current
Three-phase current
Short circuit
Additional short-circuit protection is required in the main circuit
Accuracy of current measurement (in the range of 1 x minimum
current setting
I
u
to 8 x max. current setting
I
o
)
%
3
Typical voltage measuring range
• Phase-to-phase voltage/line-to-line voltage (e.g.
U
L1 L2
)
V
110 ... 690
• Phase voltage (e.g.
U
L1 N
)
V
65 ... 400
Accuracy
• Voltage measurement (phase voltage
U
L
in the range 230 ...
400 V) %
3 (typical)
• Power factor measurement (in the rated load range p.f. = 0.4 ...
0.8) %
5 (typical)
• Apparent power measurement (in the rated load range)
%
5 (typical)
Notes on voltage measurement
• In insulated, high-resistance or asymmetrically grounded forms of
power supply system and for single-phase systems
In these networks the current/voltage measuring module can be used only
with an upstream decoupling module on the system interface.
• Supply lines for voltage measurement
In the supply lines from the main circuit for voltage measurement of
SIMOCODE pro it may be necessary to provide additional line protection!
Digital modules or multifunction modules
Type
3UF7300, 3UF7310, 3UF7600
Control circuit
Rated insulation voltage
U
i
V
300 (at pollution degree 3)
Rated impulse withstand voltage
U
imp
kV
4
Relay outputs
• Number
2 monostable or bistable relay outputs (depending on the version)
• Specified short-circuit protection for auxiliary contacts
(relay outputs)
-
Fuse links
6 A operational class gG; 10 A quick-response (IEC 60947-5-1)
-
Miniature circuit breaker
1.6 A, C characteristic (IEC 60947-5-1); 6 A, C characteristic (Ik <500 A)
• Rated uninterrupted current
A
6
• Rated switching capacity
- AC-15
6 A/24 V AC
6 A/ 120 V AC
3 A/ 230 V AC
- DC-13
2 A/24 V DC
0.55 A/60 V DC
0.25 A/125 V DC
Inputs (binary)
4 inputs, electrically isolated, supplied externally with 24 V DC or
110 ... 240 V AC/DC depending on the version, connected to a common potential
Ground-fault modules or multifunction modules
Type
3UF7510, 3UF7600
Control circuit
Connectable residual-current transformer
3UL23
Type of current for monitoring
Type A (AC and pulsating DC residual currents)
Adjustable response value
30 mA ... 40 A
Relative measurement error
%
7.5
Temperature modules or multifunction modules
Type
3UF7600, 3UF7700
Sensor circuit
Number of temperature sensors
• 3UF7700
3 temperature sensors
• 3UF7600
1 temperature sensor
Typical sensor current
• PT100
mA
1 (typical)
• PT1000/KTY83/KTY84/NTC
mA
0.2 (typical)
Open-circuit/short-circuit detection
• Sensor type
PT100/PT1000
KTY83-110
KTY84
NTC
-
Open circuit
✓
✓
✓
--
-
Short circuit
✓
✓
✓
✓
-
Measuring range
°C
-50 ... +500
-50 ... +175
-40 ... +300
80 ... 160
Measuring accuracy at 20 °C ambient temperature
(T20)
K
<
2
Deviation due to ambient temperature
(in % of measuring range)
%
0.05 per K deviation from T20
Conversion time
ms
500
Connection type
Two- or three-wire connection