SIEMENS
10/10
Siemens IC 10 · 2017
SIMOCODE 3UF Motor Management and Control Devices
SIMOCODE pro 3UF7 Motor Management and Control Devices
General data
10
■
Technical specifications
More information
Technical specifications
, see
"SIMOCODE pro PROFIBUS" System Manual,
see
"SIMOCODE pro V PROFINET" System Manual,
see
"SIMOCODE pro Modbus RTU" Configuration Manual,
see
"SIMOCODE pro Safety Fail-Safe Digital Modules" System Manual,
see
Application Manual "SIRIUS Controls with IE3/IE4 motors",
see
General data
Type
3UF7
Permissible ambient temperature
• During operation
°C
-25 ... +60; 3UF721: 0 ... +60
• During storage and transport
°C
-40 ... +80; 3UF721: -20 ... +70
Degree of protection (acc. to IEC 60529)
• Measurement modules with busbar connection
IP00
• Operator panel (front) and door adapter (front) with cover
IP54
• Other components
IP20
Shock resistance (sine pulse)
g
/ms
15/11
Mounting position
Any
Frequency
Hz
50/60
5 %
EMC interference immunity (according to IEC 60947-1)
Corresponds to degree of severity 3
• Conducted interference, burst acc. to IEC 61000-4-4
kV
kV
2 (power ports)
1 (signal ports)
• Conducted interference, high frequency acc. to IEC 61000-4-6
V
10
• Conducted interference, surge acc. to IEC 61000-4-5
kV
kV
2 (line to ground); 3UF7320-1AB, 3UF7330-1AB: 1 (line to ground)
1 (line to line); 3UF7320-1AB, 3UF7330-1AB: 0.5 (line to line)
• Electrostatic discharge, ESD acc. to IEC 61000-4-2
kV
kV
8 (air discharge); 3UF7020: Operator input during operation only on the front
6
(contact discharge); 3UF721: 4
(contact discharge)
• Field-related interference acc. to IEC 61000-4-3
V/m
10
EMC emitted interference (according to IEC 60947-1)
• Conducted and radiated interference emission
EN 55011/EN 55022 (CISPR 11/CISPR 22)
(Corresponds to degree of severity A)
Protective separation (acc. to IEC 60947-1)
All circuits in SIMOCODE pro are safely separated from each other according
to IEC 60947-1, i.e. they are designed with doubled creepage paths and
clearances. In this context, compliance with the instructions in the test report
"Safe Isolation" No. 2668 is required.
Basic units
Type
3UF7000-1AU00-0, 3UF7010-1AU00-0
3UF7011-1AU00-0, 3UF7020-1AU01-0
3UF7012-1AU00-0
3UF7000-1AB00-0, 3UF7010-1AB00-0
3UF7011-1AB00-0, 3UF7020-1AB01-0
3UF7012-1AB00-0
Control circuit
Rated control supply voltage
U
s
(acc. to IEC 61131-2)
110 ... 240 AC/DC; 50/60 Hz
24 V DC
Operating range
• SIMOCODE pro C (3UF7000) and SIMOCODE pro V
(3UF7010/3UF7012)
0.85 ... 1.1 x
U
s
0.80 ... 1.2 ×
U
s
• SIMOCODE pro V PN (3UF7011) and SIMOCODE pro S
(3UF7020)
- Operation
0.85 ... 1.1 x
U
s
0.80 ... 1.2 ×
U
s
-
Start up
0.85 ... 1.1 x
U
s
0.85 ... 1.2 ×
U
s
Power consumption
• SIMOCODE pro C (3UF7000) and SIMOCODE pro S (3UF7020)
7 VA/5 W
5 W
• SIMOCODE pro V (3UF7010/3UF7012)
incl. two connected expansion modules
10 VA/7 W
7 W
• SIMOCODE pro V PN (3UF7011)
incl. two connected expansion modules
11 VA/8 W
8 W
Rated insulation voltage
U
i
V
300 (for pollution degree 3)
Rated impulse withstand voltage
U
imp
kV
4
Relay outputs
• Number
-
SIMOCODE pro C, SIMOCODE pro V, SIMOCODE pro V PN
3 monostable relay outputs
- SIMOCODE pro S
2 monostable relay outputs
• Specified short-circuit protection for auxiliary contacts
(relay outputs)
-
Fuse links
6 A operational class gG; 10 A quick-response (IEC 60947-5-1)
-
Miniature circuit breaker
1.6 A, C characteristic (IEC 60947-5-1); 6 A, C characteristic (Ik < 500 A)
• Rated uninterrupted current
A
6
• Rated switching capacity
- AC-15
6 A/24 V AC
6 A/ 120 V AC
3 A/ 230 V AC
- DC-13
2 A/24 V DC
0.55 A/60 V DC
0.25 A/125 V DC
Inputs (binary)
4 inputs supplied internally by the device electronics (with 24 V DC)
and connected to a common potential
Thermistor motor protection (binary PTC)
• Summation cold resistance
k
1.5
• Response value
k
3.4 ... 3.8
• Return value
k
1.5 ... 1.65
© Siemens AG 2016