SIEMENS
10/5
Siemens IC 10 · 2017
SIMOCODE 3UF Motor Management and Control Devices
SIMOCODE pro 3UF7 Motor Management and Control Devices
General data
10
■
Overview
SIMOCODE pro S for efficient entry into motor management and
SIMOCODE pro V for maximum functionality
SIMOCODE pro is a flexible, modular motor management
system for motors with constant speeds in the low-voltage
performance range. It optimizes the connection between
I&C and motor feeder, increases plant availability and allows
significant savings to be made for installation, commissioning,
operation and maintenance of a system.
When SIMOCODE pro is installed in the low-voltage switch-
board, it is the intelligent interface between the higher-level
automation system and the motor feeder and includes the
following:
•
Multifunctional, solid-state full motor protection that is
independent of the automation system
•
Integrated control functions instead of hardware for the motor
control
•
Detailed operational, service and diagnostics data
•
Open communication through PROFIBUS DP, PROFINET,
Modbus RTU and OPC UA
•
Safety relay function for the fail-safe disconnection of motors
up to SIL 3 (IEC 61508, IEC 62061) or PL e with Category 4
(EN ISO 13849-1)
•
SIMOCODE ES is the software package for SIMOCODE pro
parameterization, start up and diagnostics.
Device series
SIMOCODE pro is structured into several functionally tiered
series:
•
SIMOCODE pro C, as a compact system for direct-on-line
starters and reversing starters or for controlling a motor starter
protector.
•
SIMOCODE pro S – the smart system for direct-on-line,
reversing, and wye-delta starters or for controlling a motor
starter protector or soft starter. Its expandability with a multi-
function module provides comprehensive input/output project
data volume, precise ground-fault detection via the 3UL23
residual-current transformers and temperature measurement.
•
SIMOCODE pro V, as a variable system with all control func-
tions and with the possibility of expanding the inputs, outputs
and functions of the system at will using expansion modules.
✓
Available
--
Not available
1)
Maximum of 5 expansion modules.
2)
When an operator panel with display and/or a decoupling module are
used, more restrictions on the number of expansion modules connectable
per basic unit must be observed;
see page 10/13
.
3)
The fail-safe digital module can be used instead of one of the two digital
modules.
Per feeder each system always comprises one basic unit and
one separate current measuring module. The two modules are
connected together electrically through the system interface
with a connection cable and can be mounted mechanically con-
nected as a unit (one behind the other) or separately (side by
side). The motor current to be monitored is decisive only for the
choice of the current measuring module.
An operator panel for mounting in the control cabinet door is op-
tionally connectable through a second system interface on the
basic unit. Both the current measuring module and the operator
panel are electrically supplied by the basic unit through the con-
nection cable. More inputs, outputs and functions can be added
to the SIMOCODE pro V and SIMOCODE pro S by means of op-
tional expansion modules, thus supplementing the inputs and
outputs already existing on the basic unit. With the DM-F Local
and DM-F PROFIsafe fail-safe digital modules it is also possible
to integrate the fail-safe disconnection of motors in the
SIMOCODE pro V motor management system.
All modules are connected by connection cables. The connec-
tion cables are available in various lengths. The maximum dis-
tance between modules (e.g. between the basic unit and the
current measuring module) must not exceed 2.5 m. The total
length of all the connection cables per system interface of the
basic unit may be up to 3 m.
Note:
SIMOCODE pro can also be found in the TIA Selection Tool.
The various system components can therefore be conveniently
selected.
See
www.siemens.com/tia-selection-tool
.
More information
Home page,
see www.siemens.com/sirius
Industry Mall,
see www.siemens.com/product?3UF7
Expansion
possibilities
SIMOCODE
pro C
pro S
pro V
1)
PROFIBUS
PROFIBUS
PROFIBUS
2)
Modbus RTU
2)
PROFINET
Operator panels
✓
✓
✓
✓
Operator panels
with display
--
--
✓
✓
Current measuring
modules
✓
✓
✓
✓
Current/voltage
measuring
modules
--
--
✓
✓
Decoupling
modules
--
--
✓
✓
Expansion
modules:
• Digital modules
--
--
2
2
• Fail-safe digital
modules
3)
--
--
1
1
• Analog module
--
--
1
2
• Ground-fault
module
--
--
1
1
• Temperature
module
--
--
1
2
• Multifunction
modules
--
1
--
--
© Siemens AG 2016