SIEMENS
9/51
Siemens IC 10 · 2017
Motor Starters for Use in the Field, High Degree of Protection
SIRIUS M200D Motor Starters
M200D Motor Starters for PROFIBUS/PROFINET
General data
9
1)
Integrated brake control supplies DC power supply for the brake.
Line voltage
380 V AC
400 V AC
440 V AC
480 V AC
500 V AC
Brake voltage with brake control 180 V DC
1)
Operational voltage
V
230/400 AC or 180 DC
Uninterrupted current
A
< 0.5 at 230/400 V AC, < 0.8 at 180 V DC
Short-circuit protection
Yes, 1 A melting fuse
Rectified brake voltage
171 V DC
180 V DC
198 V DC
216 V DC
225 V DC
Recommended brake coil voltage for Siemens motors
170 ... 200 V DC
170 ... 200 V DC
184 ... 218 V DC
184 ... 218 V DC
--
Type
M200D communication modules
For PROFIBUS
For PROFINET
Mechanics and environment
Mounting dimensions (W x H x D)
mm
174 x 139 x 40
Permissible ambient temperature
• During operation
°C
-25 ... +55
• During storage
°C
-40 ... +70
Weight
g
300
Permissible mounting position
Vertical, horizontal, lying
Vibration resistance acc. to IEC 60068 Part 2-6
g
2
Shock resistance
• Acc. to IEC 60068 Part 2-27
g
/ms
12/11 half-sine
• Without influencing the contact position
g
/ms
9.8/5 or 5.9/10
Degree of protection acc. to IEC 529
IP65
Installation altitude
• Up to 1 000 m
No derating
• Up to 2 000 m
1 % per 100 m
Cooling
Convection
Protection class IEC 536 (VDE 0106-1)
1
Electrical specifications
Control circuit
Operational voltage
•
U
DC24V-NS
V DC
20.4 ... 28.8
•
U
DC24V-S
V DC
20.4 ... 28.8
Power consumption from
•
U
DC24V-NS
mA
< 300
•
U
DC24V-S
mA
< 100
© Siemens AG 2016