SIEMENS
9/50
Siemens IC 10 · 2017
Motor Starters for Use in the Field, High Degree of Protection
SIRIUS M200D Motor Starters
M200D Motor Starters for PROFIBUS/PROFINET
General data
9
■
Technical specifications
1)
DS
....
Direct-on-line starters
RS
....
Reversing starters
DSS .. Direct-on-line soft starters
RSS .. Reversing soft starters
te
......
Full motor protection (thermal + electronic)
s
.......
Electronic switching with semiconductor.
2)
.
3)
Only systems with grounded neutral point permitted.
More information
Device manual for M200D PROFIBUS/PROFINET,
see
FAQs,
Note on security:
In order to protect plants, systems, machines and networks against cyber
threats, it is necessary to implement – and continuously maintain – a holistic,
state-of-the-art industrial security concept. Siemens products and solutions
only represent one component of such a concept.
For more information about the subject of Industrial Security,
see
www.siemens.com/industrialsecurity
.
Type
M200D PROFIBUS/PROFINET motor starter modules
Electromechanical switching
Electronic switching
Technology designation
1)
DSte/RSte
sDSSte/sRSSte
Mechanics and environment
Mounting dimensions (W x H x D)
• Without communication module
mm
294 x 215 x 159
• With communication module
mm
295 x 215 x 163
Permissible ambient temperature
• During operation
°C
-25 ... +55
• During storage
°C
-40 ... +70
Weight
g
2 820/3 080
3 160/3 360
Permissible mounting position
Vertical, horizontal, lying
Vibration resistance acc. to IEC 60068 Part 2-6
g
2
Shock resistance
• Acc. to IEC 60068 Part 2-27
g
/ms
12/11 half-sine
• Without influencing the contact position
g
/ms
9.8/5 or 5.9/10
Degree of protection acc. to IEC 529
IP65
Installation altitude
• Up to 1 000 m
No derating
• Up to 2 000 m
1 % per 100 m
Cooling
Convection
Protection class IEC 536 (VDE 0106-1)
1
Electrical specifications
Main circuit
Maximum power of three-phase motors at 400 V AC
kW
5.5
Rated operational voltage
U
e
• Approval acc. to EN 60947-1
V AC
400 (50/60 Hz)
• Approval acc. to UL and CSA
V AC
600 (50/60 Hz)
480 (50/60 Hz)
• Rated operational current range
A
0.15 ... 2 / 1.5 ... 12
--
• Rated operational current range for soft start
A
--
0.15 ... 2 / 1.5 ... 12
• Rated operational current range for direct start
A
--
0.15 ... 2 /1.5 ... 9
Rated operational current for starters
I
e
at 400 V AC
• 400 V at AC-1 / 2 / 3
A
12
--
• 500 V at AC-1 / 2 / 3
A
9
--
• 400 V at AC-4
A
4
--
• 400 V at AC-53a
A
--
12 for soft starting,
9 for direct-on-line starting
Mechanical endurance of contactor
Operating cycles
30 million
--
Trip class
CLASS 5, 10, 15, 20
Permissible switching frequency
See manual
2)
Rated ultimate short-circuit breaking capacity
I
q
• At 400 V AC
kA
50
• At 500 V AC
kA
50
20
3)
Short-circuit protection
• At
I
emax
= 2 A
integrated, 2 x13
I
e
= 26 A
• At
I
emax
= 9 /12 A
integrated, 2 x13
I
e
= 208 A
© Siemens AG 2016