Motor Starters for Use in the Field, High Degree of Protection
SIRIUS M200D Motor Starters
M200D Motor Starters for AS-Interface
General data
9
1)
DS
....
Direct-on-line starters
RS
....
Reversing starters
DSS .. Direct-on-line soft starters
RSS .. Reversing soft starters
te
......
Full motor protection (thermal + electronic)
s
.......
Electronic switching with semiconductor.
2)
.
3)
.
4)
Only systems with grounded neutral point permitted.
Type
M200D motor starters
AS-i Basic
Electromechanical
switching
AS-i Basic
Electronic
switching
AS-i Standard
Electromechanical
switching
AS-i Standard
Electronic
switching
Technology designation
1)
DSte / RSte
sDSte / sRSte
DSte / RSte
sDSSte / sRSSte
Mechanics and environment
Mounting dimensions (W x H x D)
mm
294 x 215 x 159
Permissible ambient temperature
• During operation
°C
-25 ... +55
• During storage
°C
-40 ... +70
Weight
g
2 880/3 130
3 220/3 420
2 880/3 130
3 220/3 420
Permissible mounting position
Vertical, horizontal, lying
Vibration resistance acc. to IEC 60068 Part 2-6
g
2
Shock resistance
• Acc. to IEC 60068 Part 2-27
g
/ms
12/11 half-sine
• Without influencing the contact position
g
/ms
9.8/5 or 5.9/10
Degree of protection acc. to IEC 529
IP65
Installation altitude
• Up to 1 000 m
No derating
• Up to 2 000 m
1 % per 100 m
Cooling
Convection
Protection class IEC 536 (VDE 0106-1)
1
Electrical specifications
Control circuit
Operating voltage
U
As-i
V DC
26.5 ... 31.6
Supply voltage
U
aux
V DC
20.4 ... 28.8
Power consumption from AS-i (incl. 200 mA sensor supply)
mA
< 300
Current consumption from
U
aux
(without digital output)
• Max.
mA
155
15 (direct-on-line)/
175 (reversing)
155
15 (direct-on-line)/
175 (reversing)
• Typ.
mA
75
10 (direct-on-line)/
75 (reversing)
75
10 (direct-on-line)/
75 (reversing)
Main circuit
Maximum power of three-phase motors at 400 V AC
kW
5.5
4
5.5
5.5
Rated operational voltage
U
e
• Approval acc. to EN 60947-1
V AC
400 (50/60 Hz)
• Approval acc. to UL and CSA
V AC
600 (50/60 Hz)
480 (50/60 Hz)
600 (50/60 Hz)
480 (50/60 Hz)
• Rated operational current range
A
0.15 ... 2 / 1.5 ... 12
--
0.15 ... 2 / 1.5 ... 12
--
• Rated operational current range for soft start
A
--
0.15 ... 2 / 1.5 ... 12
• Rated operational current range for direct start
A
--
0.15 ... 2 /1.5 ... 9
--
0.15 ... 2 /1.5 ... 9
Rated operational current for starters
I
e
at 400 V AC
• 400 V at AC-1 / 2 / 3
A
12
--
12
--
• 500 V at AC-1 / 2 / 3
A
9
--
9
--
• 400 V at AC-4
A
4
--
4
--
• 400 V at AC-53a
A
--
9
--
12 for soft start
9 for direct start
Mechanical endurance of contactor
Operating cycles
30 million
--
30 million
--
Trip class
CLASS 10
CLASS 5, 10, 15, 20
Type of coordination acc. to IEC 60947-4-1
1 (2 for device
version 2A)
1
1 (2 for device
version 2A)
1
Permissible switching frequency
See manual
2)3)
Rated ultimate short-circuit breaking capacity
I
q
• At 400 V AC
kA
50
• At 500 V AC
kA
50
4)
20
4)
50
20
4)
Short-circuit protection
• At
I
emax
= 2 A
integrated, 2 x13
I
e
= 26 A
• At
I
emax
= 9 /12 A
integrated, 2 x13
I
e
= 208 A
Brake actuation (option)
Operational voltage
V
230/400 AC or 180 DC
Uninterrupted current
A
< 0.5 at 230/400 V AC
< 0.8 at 180 V DC
Short-circuit protection
Yes, 1 A melting fuse
© Siemens AG 2016