SIEMENS
9/12
Siemens IC 10 · 2017
Motor Starters for Use in the Field, High Degree of Protection
ET 200pro Motor Starters
ET 200pro safety Motor Starters Solutions local/PROFIsafe
Safety modules local
9
■
Technical specifications
Type
Safety local isolator module
400 V disconnecting module
General data
Mounting dimensions (W x H x D) in mm
• Direct-on-line starters and reversing starters
mm
110 x 230 x 170
110 x 230 x 150
Permissible ambient temperature
• During operation
°C
-25 ... +55
• During storage
°C
-40 ... +70
Permissible mounting position
Any
Vibration resistance acc. to IEC 60068, Part 2-6
2
g
Shock resistance acc. to IEC 60068, Part 2-27
Half-sine 15
g
/11 ms
Power consumption
• From auxiliary circuit L+/M (U1)
mA
Approx. 20
• From auxiliary circuit A1/A2 (U2)
--
Rated operational current
I
e
for power bus
A
25
Rated operational voltage
U
e
V
400 (50/60 Hz)
Approval DIN VDE 0106, Part 101
V
Up to 500
CSA and UL approval
V
Up to 600
Conductor cross-sections
Incoming power supply
mm
2
max. 6 x 4
Degree of protection
IP65
Touch protection
Finger-safe
Pollution degree
3, IEC 60664 (IEC 61131)
Rated impulse withstand voltage
U
imp
kV
6
Rated insulation voltage
U
i
V
400
Rated operational current
I
e
for starters
• AC-1/2/3 at 40 °C
-
At 400 V
A
16
25
-
At 500 V
A
16
25
Rated short-circuit breaking capacity
kA
50 at 400 V
Type of coordination acc. to IEC 60947-4-1
2
Protective separation between main and auxiliary circuits
V
400,
Acc. to DIN VDE 0106 Part 101
Switching times at 0.85 ... 1.1 x
U
e
• Closing delay
ms
--
25 ... 100
• Opening delay
ms
--
7 ... 10
Device functions
• Group diagnostics
Yes, parameterizable
Device indications
• Group fault
SF LED (red)
© Siemens AG 2016