SIEMENS
9/5
Siemens IC 10 · 2017
Motor Starters for Use in the Field, High Degree of Protection
ET 200pro Motor Starters
General data
9
✓
Function available
--
Function not available
1)
DS
....
Direct-on-line starters
RS
....
Reversing starters
DSS ..
Direct-on-line soft starters
RSS ..
Reversing soft starters
e
.......
Electronic motor protection
te
......
Full motor protection (thermal + electronic)
s
.......
Electronic switching with semiconductor.
Type
Standard motor starters
High Feature motor starters
Technology designation
1)
DSe, RSe
DSe, RSe
sDSSte, sDSte,
sRSSte, sRSte
Device functions (firmware features)
Parameterizable rated operational current
✓
Integrated short-circuit protection
✓
Parameterizable current limit values
--
✓
2 limit values
Parameterizable response in case of current limit violation
--
✓
Zero current monitoring
✓
Parameterizable response in case of zero current violation
✓
Parameterizable current unbalance limit
%
-- Fixed limit value
(30 x
I
e
)
✓
30 ... 60 x
I
e
Parameterizable response in case of unbalance limit violation
✓
Motor blocking monitoring
--
✓
Parameterizable blocking current limit
%
--
✓
150 ... 1 000 x
I
e
Parameterizable blocking time limit
s
--
✓
1 ... 5
Current value transmission
✓
Group warning diagnostics
--
✓
Parameterizable
Group diagnostics
✓
Parameterizable
EMERGENCY START
✓
Digital inputs
--
✓
4 inputs
• Parameterizable input signal
--
✓
Latching/non-latching
• Parameterizable input level
--
✓
NC/NO
• Parameterizable input signal delay
ms
--
✓
10 ... 80
• Parameterizable input signal extension
ms
--
✓
0 ... 200
• Parameterizable input control actions
--
✓
12 different actions
Brake output (400 V AC)
✓
Order option
Parameterizable brake enabling delay
s
✓
-2.5 ... +2.5
Parameterizable holding time of the brake during stopping
s
✓
0 ... 25
Parameterizable start up type
--
✓
Parameterizable ramp-down time
--
✓
Parameterizable starting voltage
--
✓
Parameterizable stopping voltage
--
✓
Local device interface
✓
Firmware update
✓
By specialists
Thermal motor model
✓
Parameterizable trip class
-- CLASS 10 fixed
✓
CLASS 5, 10, 15, 20
Parameterizable response in case of overload of thermal motor model
--
✓
3 possible states
Advance warning limit for motor heating
%
--
✓
Parameterizable 0 ... 95
Advance warning limit time-related trip reserve
s
--
✓
Parameterizable 0 ... 500
Parameterizable recovery time
min
--
✓
1 ... 30
Parameterizable protection against voltage failure
-- Permanently integrated
✓
Reversing start function
✓
Order option
Parameterizable interlock time for reversing starters
-- 150 ms fixed
✓
0 ... 60 s
Integrated logbook functions
✓
3 device logbooks
Integrated statistics data memory
✓
Parameterizable response in case of CPU/master stop
✓
PROFIenergy profile support
• Disconnection of the motor current during idle times
✓
• Measured motor current values
✓
Device indications
• Group fault
SF LED (red)
• Switching state
STATE LED (red, yellow, green)
• Device status
DEVICE LED (red, yellow, green)
• Digital inputs
--
IN 1 ... IN 4, LED
© Siemens AG 2016