Siemens IC 10 · 2017
Motor Starter Protectors/Circuit Breakers
SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers
General data
7
Voltage transformer circuit breakers
1)
If two different conductor cross-sections are connected to one clamping
point, both cross-sections must be in the range specified.
General data
Type
3RV1611-1AG14
3RV1611-1CG14
3RV1611-1DG14
Size
S00
S00
S00
Dimensions (W x H x D)
mm
45 x 90 x 70
45 x 90 x 70
45 x 90 x 70
Rated current
I
n
A
1.4
2.5
3
Ambient temperature
• During storage/transport
°C
–50 ... +80
• During operation
°C
–20 ... +60 (up to +70 °C possible with current reduction)
Rated operational voltage
U
e
V
400
Rated frequency
Hz
16.66 ... 60
Rated insulation voltage
U
i
V
690
Short-circuit breaking capacity
I
cu
at 400 V AC
kA
50
Set value of the thermal overload release
A
1.4
2.5
3
Response value of the instantaneous overcurrent release
A
6
20 %
10.5
20 %
20
20 %
Tripping time
of the instantaneous overcurrent release
ms
Approx. 6 at 12 A
Approx. 6 at 20 A
Approx. 6 at 40 A
Internal resistance
• In cold state
> 0.25
6.5 %
• In heated state
> 0.30
6.5 %
Shock resistance
acc. to IEC 60068-2-27
g
/ms
15
Degree of protection
acc. to IEC 60529
IP20
Touch protection
acc. to EN 50274
Finger-safe for vertical contact from the front
Endurance
• Mechanical
Operating cycles
10 000
• Electrical
Operating cycles
10 000
Permissible mounting position
Any
W
H
D
Type
3RV1611-1AG14
3RV1611-1CG14
3RV1611-1DG14
Conductor cross-sections, main circuit, 1 or 2 conductors
Connection type
Screw terminals
Terminal screw
Pozidriv size 2
Conductor cross-sections (min./max.),
1 or 2 conductors can be connected
• Solid or stranded
mm
2
2 x (0.5 ... 1.5)
1)
, 2 x (0.75 ... 2.5)
1)
, 2 x (1 ... 4)
• Finely stranded with end sleeve (DIN 46228-1)
mm
2
2 x (0.5 ... 1.5)
1)
, 2 x (0.75 ... 2.5)
1)
Auxiliary switches for blocking the distance protection
With defined lateral assignment for blocking
distance protection
1 CO (for use as 1 NO or 1 NC)
Rated operational voltage
U
e
Alternating voltage
V
125
Rated operational current
I
e
/AC-14
At
U
e
= 125 V
A
0.1
Rated operational voltage
U
e
Direct voltage
L/R
200 ms
V
60
Rated operational current
I
e
/DC-13
At
U
e
= 60 V
A
0.3
Minimum load capacity
V
5
mA
1
Short-circuit protection for auxiliary circuit
Melting fuse
A
250 V type FF 2A (prospective short-circuit current < 1.1 kA)