SIEMENS
6/94
Siemens IC 10 · 2017
Solid-State Switching Devices for Resistive/Inductive Loads
Function Modules
General data
6
■
Technical specifications
1)
Note limitations for power controller function modules. These modules
were built as Class A devices. The use of these devices in residential areas
could result in lead in radio interference. In this case these may be
required to introduce additional interference suppression measures.
1)
Versions are independent of the main circuit.
More information
System Manual and Manual,
see
FAQs,
Type
3RF29..-0EA..
3RF29..-0FA..
3RF29..-0GA..
3RF29..-0HA..
3RF29..-0JA..
3RF29..-0KA..
Dimensions (W x H x D)
mm
22.5 x 84 x 38
22.5 x 102 x 39
45 x 112 x 44
45 x 112 x 44
45 x 112 x 44
45 x 112 x 44
General data
Ambient temperature
• During operation, derating from 40 °C
°C
-25 ... +60
• During storage
°C
-55 ... +80
Installation altitude
m
0 ... 1 000; derating from 1 000
Shock resistance
acc. to IEC 60068-2-27
g
/ms
15/11
Vibration resistance
acc. to IEC 60068-2-6
g
2
Degree of protection
IP20
Electromagnetic compatibility (EMC)
• Emitted interference
-
Conducted interference voltage
Acc. to IEC 60947-4-3
Class A for industrial applications
1)
-
Emitted, high-frequency interference
voltage according to IEC 60947-4-3
Class B for residential, business and commercial applications
• Interference immunity
-
Electrostatic discharge
acc. to IEC 61000-4-2
(corresponds to degree of severity 3)
kV
Contact discharge 4; air discharge 8; behavior criterion 2
-
Induced RF fields
acc. to IEC 61000-4-6
MHz
0.15 ... 80; 140 dB
V; behavior criterion 1
-
Burst acc. to IEC 61000-4-4
2 kV/5.0 kHz; behavior criterion 2
-
Surge acc. to IEC 61000-4-5
kV
Conductor - ground 2; conductor - conductor 1; behavior criterion 2
Connection type
Auxiliary/control contacts
Screw terminals
• Conductor cross-section
mm
2
1 x (0.5 ... 2.5), 2 x (0.5 ... 1.0), 1 x (AWG 20 ... 12)
• Stripped length
mm
7
• Terminal screw
M3
• Tightening torque
Nm
0.5 ... 0.6
lb.in
4.5 ... 5.3
Connection type
Converters
Straight-through transformers
• Diameter
mm
--
7
17
Type
3RF29..-0EA18
3RF29..-0FA08
3RF29..-0GA.3
3RF29..-0GA.6
Main circuit
Rated operational voltage
U
e
V AC
--
1)
110 ... 230
400 ... 600
• Operating range
V AC
--
93.5 ... 253
340 ... 660
• Rated frequency
Hz
--
50/60
Rated insulation voltage
U
i
V
--
600
Voltage measuring
• Measuring range
V
--
93.5 ... 253
340 ... 660
Mains voltage,
fluctuation
compensation
%
--
20
Type
3RF29..-0HA.3
3RF29..-0KA.3
3RF29..-0HA.6
3RF29..-0KA.6
3RF29..-0JA.3
3RF29..-0JA.6
Main circuit
Rated operational voltage
U
e
V AC
110 ... 230
400 ... 600
110 ... 230
400 ... 600
• Operating range
V AC
93.5 ... 253
340 ... 660
93.5 ... 253
340 ... 660
• Rated frequency
Hz
50/60
Rated insulation voltage
U
i
V
600
Voltage measuring
• Measuring range
V
93.5 ... 253
340 ... 660
93.5 ... 253
340 ... 660
Mains voltage,
fluctuation
compensation
%
20
© Siemens AG 2016