Solid-State Switching Devices for Resistive/Inductive Loads
Solid-State Relays
SIRIUS 3RF20 solid-state relays, single-phase, 45 mm
6
■
Overview
Single-phase solid-state relays (without heat sink) with a width of 45 mm
The solid-state relays with a width of 45 mm provide for
connection of the power supply lead and the load from above.
This makes it easy to replace existing solid-state relays in
existing arrangements.
The connection of the control cable is as space-saving as the
22.5 mm design, as it is simply plugged on.
■
Technical specifications
1)
If two different conductor cross-sections are connected to one clamping
point, both cross-sections must lie in one of the ranges specified.
More information
System Manual and Manual,
see
FAQs,
Type
3RF20..-1
....
3RF20..-4
....
Dimensions (W x H x D)
mm
45 x 58 x 48
45 x 58 x 48
General data
Ambient temperature
• During operation, derating from 40 °C
°C
-25 ... +60
• During storage
°C
-55 ... +80
Installation altitude
m
0 ... 1 000; derating from 1 000
Shock resistance
acc. to IEC 60068-2-27
g
/ms
15 /11
Vibration resistance
acc. to IEC 60068-2-6
g
2
Degree of protection
IP20
Electromagnetic compatibility
(EMC)
• Emitted interference
-
Conducted interference voltage
acc. to IEC 60947-4-3
Class A for industrial applications
-
Emitted, high-frequency interference voltage
acc. to IEC 60947-4-3
Class B for residential, business and commercial applications
• Interference immunity
-
Electrostatic discharge
acc. to IEC 61000-4-2
(corresponds to degree of severity 3)
kV
Contact discharge 4; air discharge 8; behavior criterion 2
-
Induced RF fields
acc. to IEC 61000-4-6
MHz
0.15 ... 80; 140 dBμV; behavior criterion 1
-
Burst acc. to IEC 61000-4-4
kV
2/5.0 kHz; behavior criterion 2
-
Surge acc. to IEC 61000-4-5
kV
Conductor - ground 2; conductor - conductor 1; behavior criterion 2
Mounting
• Screws (not included in the scope of supply)
2 x M4
• Tightening torques
Nm
1.5
Connection type
Screw terminals
Spring-type terminals
Connection, main contacts
• Conductor cross-sections
- Solid
mm
2
2 x (1.5 ... 2.5)
1)
, 2 x (2.5 ... 6)
1)
--
-
Finely stranded with end sleeve
mm
2
2 x (1 ... 2.5)
1)
, 2 x (2.5 ... 6)
1)
, 1 x 10
--
-
Solid or stranded, AWG cables
2 x (AWG 14 ... 10)
--
• Terminal screw
M4
--
• Tightening torque
Nm
2 ... 2.5
--
lb.in
7 ... 10.3
--
Connection, auxiliary/control contacts
• Conductor cross-sections
mm
2
1 x (0.5 ... 2.5), 2 x (0.5 ... 1.0),
AWG 20 ... 12
0.5 ... 2.5
AWG 20 ... 12
• Stripped length
mm
7
10
• Terminal screw
M3
--
• Tightening torque
Nm
0.5 ... 0.6
--
lb.in
4.5 ... 5.3
--
W
H
D