SIEMENS
6/12
Siemens IC 10 · 2017
SIRIUS 3RW Soft Starters
3RW30, 3RW40 for Standard Applications
3RW30
General data
6
1)
The rated motor current (specified on the motor's name plate) should at
least amount to the specified percentage of the SIRIUS soft starter unit's
rated operational current
I
e
.
2)
If this value is exceeded, problems with line capacities may arise, which
can result in false firing.
Type
3RW3003-1CB54
3RW3003-2CB54
Mechanics and environment
Mounting dimensions (W x H x D)
• Screw terminals
mm
22.5 x 100 x 120
--
• Spring-type terminals
mm
--
22.5 x 101.6 x 120
Permissible ambient temperature
During operation
°C
-25 ... +60; (derating from +40)
During storage
°C
-40 ... +80
Weight
kg
0.207
0.188
Permissible mounting position
Permissible installation altitude
m
5 000
(Derating from 1 000,
see "Characteristic Curves", page 6/8
); higher on
request
Degree of protection
acc. to IEC 60529
IP20 (IP00 terminal compartment)
Control electronics
Rated values
Rated control supply voltage
V
24 ... 230 AC/DC
• Tolerance
%
10
Rated frequency at AC
Hz
50/60
• Tolerance
%
10
Power electronics
Rated operational voltage
V AC
200 ... 400
Tolerance
%
10
Rated frequency
Hz
50/60
Tolerance
%
10
Uninterrupted duty
(% of
I
e
)
%
100
Minimum load
1)
(% of
I
e
); at 40 °C
%
9
Maximum conductor length
between soft starter and motor
m
100
2)
Load rating with rated operational current
I
e
• According to IEC and UL/CSA for individual mounting
at 40 / 50 / 60 °C, AC-53a
A
3/2.6/2.2
• According to IEC and UL/CSA for side-by-side-mounting
at 40 / 50 / 60 °C, AC-53a
A
2.6/2.2/1.8
Power loss
• In operation after completed starting with uninterrupted rated
operational current (40 °C) approx.
W
6.5
• At utilization of maximum switching frequency
W
3
Permissible starts per hour (cannot be increased by using a fan)
• For intermittent duty S4
T
u
= 40 °C, stand-alone installation vertical
1/h
1 500
• ON period = 70 % for 300 %
I
e
1/s
0.2
Dead time after uninterrupted duty
with
I
e
before restart
s
0
W
H
D
10°
10°
10°
10°
NSB0_01897