Contactor Relays
SIRIUS 3RH2 contactor relays, 4- and 8-pole
5
1)
The additional load module 3RT2916-1GA00 is recommended for higher
residual currents;
see page 3/118
.
2)
The OFF-delay of the NO contact and the ON-delay of the NC contact are
increased if the contactor coils are attenuated against voltage peaks
(suppression diode 6x to 10x; diode assembly 2x to 6x;
varistor +2 to 5 ms).
Contactor relays
Type
3RH2
Size
S00
Control
Solenoid coil operating range
• AC operation
At 50 Hz
0.8 ... 1.1 x
U
s
At 60 Hz
0.85 ... 1.1 x
U
s
• DC operation
At +50 °C
0.8 ... 1.1 x
U
s
At +60 °C
0.85 ... 1.1 x
U
s
Power consumption of the solenoid coil
(for cold coil and 1.0 x
U
s
)
• AC operation, 50 Hz
- Closing
VA/p.f.
37/0.8
- Closed
VA/p.f.
5.7/0.25
• AC operation, 60 Hz
- Closing
VA/p.f.
33/0.75
- Closed
VA/p.f.
4.4/0.25
• DC operation
Closing = Closed
W
4.0
Permissible residual current of the electronics
(with 0 signal)
• AC operation
1)
< 4 mA x (230 V/
U
s
)
• For DC operation
< 10 mA x (24 V/
U
s
)
Operating times for 1.0 x
U
s
2)
Total break time = OFF-delay + Arcing time
Values apply with coil in cold state and at operating temperature
for operating range
AC operation
• Closing
-
ON-delay of NO contact
3RH24 minimum operating time
ms
9 ... 22
ms
35
-
OFF-delay of NC contact
ms
6.5 ... 19
• Opening
-
OFF-delay of NO contact
3RH24 minimum operating time
ms
4.5 ... 15
ms
30
-
ON-delay of NC contact
ms
5 ... 15
DC operation
• Closing
-
ON-delay of NO contact
3RH24 minimum operating time
ms
35 ... 50
ms
100
-
OFF-delay of NC contact
ms
30 ... 45
• Opening
-
OFF-delay of NO contact
3RH24 minimum operating time
ms
7 ... 12
ms
30
-
ON-delay of NC contact
ms
13 ... 18
• Arcing time
ms
10 ... 15
© Siemens AG 2016