AS-Interface
Slaves
Specific Integrated Solutions
AS-Interface communication modules
2
AS-Interface communication modules for printed
circuit board installation, with direct printed circuit board
connector, without enclosure
AS-Interface communication module for printed circuit board
installation 3RK1400-1CD00-0AA2, 3RK2400-1FD00-0AA2
With the 3RK1400-1CD00-0AA2 4I/4O or 3RK2400-1FD00-0AA2
4I/3O modules
for printed circuit board mounting, it is possible
for up to four mechanical contacts or 3-conductor sensors
according to IEC 947-5-2 to be connected.
Up to four indicator lights via the 4I/4O module or up to three
indicator lights via the 4I/3O module can also be controlled.
The power for short-circuit proof solid-state switching outputs is
provided from an auxiliary voltage (24 V PELV).
Mounting is very easy using a "Card Edge Board-to-Board
Connector". This connector can be ordered for vertical and
horizontal mounting from the company AMP, for example:
•
180° version for vertical mounting (AMP):
Type 530843-2
•
90° version for horizontal mounting (AMP):
Type 650118-1
If the inputs are loaded with more than 200 mA, the module does
not respond to invoking by a master.
AS-Interface communication module for printed circuit board
installation 3RK1200-0CD00-0AA2
With the 4I module for printed circuit board mounting, it is possi-
ble for up to four mechanical contacts or 3-conductor sensors
to be connected, the power for inputs being provided from the
AS-Interface cable.
Mounting is very easy using a "Card Edge Board-to-Board
Connector". This connector can be ordered for vertical and
horizontal mounting from the company AMP, for example:
•
180° version for vertical mounting (AMP):
Type 530843-2
•
90° version for horizontal mounting (AMP):
Type 650118-1
If the inputs are loaded with more than 200 mA, the module does
not respond to invoking by a master.
■
Selection and ordering data
Connection
Connection pad
AS-i +
27, 29
AS-i -
28, 30
Sensor+
17, 18, 23, 24
Sensor-
13, 14, 19, 20
IN1
21
IN2
22
IN3
15
IN4
16
U
aux
+ (L24+)
2, 4
U
aux
– (M24)
1, 3
OUT1
9
OUT2
10
OUT3
5
OUT4
6 (not assigned for 3RK2400-1FD00-0AA2 4I/3O module)
OUT-
7, 8
Not assigned
11, 12, 25, 26
Connection
Connection pad
AS-i +
27, 29
AS-i -
28, 30
Sensor+
17, 18, 23, 24
Sensor-
13, 14, 19, 20
IN1
21
IN2
22
IN3
15
IN4
16
Not assigned
1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 25, 26
Version
Slave
type
SD
Article No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
d
3RK1400-
0CD00-0AA3
4I/4O module
(4 inputs/4 outputs)
• Supply of inputs and outputs using AS-Interface cable
(max. 200 mA)
-
Printed circuit board with solder pins,
protected by enclosure
Standard
10
3RK1400-0CD00-0AA3
1
1 unit
42C
• Supply of inputs and outputs using external auxiliary
voltage (24 V PELV)
-
Printed circuit board with solder pins,
protected by enclosure
Standard
20
3RK1400-0CD01-0AA3
1
1 unit
42C
• Supply of inputs using AS-Interface cable (max. 200 mA),
supply of outputs using external auxiliary voltage
(24 V PELV)
-
Printed circuit board with gold-plated direct connector
(Card Edge Board-to-Board Connector),
without enclosure
Standard
15
3RK1400-1CD00-0AA2
1
5 units
42C
3RK1400-
1CD00-0AA2
4I/3O module
(4 inputs/3 outputs)
• Supply of inputs using AS-Interface cable (max. 200 mA),
supply of outputs using external auxiliary voltage
(24 V PELV)
-
Printed circuit board with gold-plated direct connector
(Card Edge Board-to-Board Connector),
without enclosure
A/B
5
3RK2400-1FD00-0AA2
1
1 unit
42C
4I module
(4 inputs)
• Supply of inputs using AS-Interface cable (max. 200 mA)
-
Printed circuit board with gold-plated direct connector
(Card Edge Board-to-Board Connector),
without enclosure
Standard
15
3RK1200-0CD00-0AA2
1
1 unit
42C
© Siemens AG 2016