SIEMENS
2/109
Siemens IC 10 · 2017
IO-Link
Masters
IO-Link Master Module for ET 200SP
CM 4xIO-Link
2
■
Overview
CM 4x IO-Link communication module
•
Serial communication module for connecting up to four
IO-Link devices in accordance with the IO Link specification
V1.0 and V1.1. The IO-Link parameters are configured by
means of the Port Configuration Tool (PCT) with version V3.0
and higher.
•
Time-based IO ensures that signals are output with a precisely
defined response time. By combination of inputs and outputs,
products passing by, for example, can be measured exactly
or liquids can be perfectly dosed.
•
Supported data transmission rates
- COM1 (4.8 kBd)
- COM2 (38.4 kBd)
- COM3 (230.4 kBd)
•
Expansion limits
- Cable length: Max. 20 m
- Max. 32 bytes of input data and 32 bytes of output data per
port
- Max. 144 bytes of input data and 128 bytes of output data
per module
•
ET 200SP system functions supported
-
Exchange of IO-Link device parameters (V1.1 devices only)
and of IO-Link master parameters without a PG including
automatic backup recovery without an engineering tool by
means of redundant parameter storage on the e-coding
element
- Reparameterization during ongoing operation
- I&M identification data
- Firmware update
- PROFIenergy
•
Can be plugged onto type A0 BaseUnits (BU) with automatic
e-coding
•
LED displays
- DIAG: Operating state display (green/red) of the module
- C1..C4: Port status display (green) for ports 1, 2, 3 and 4
-
Q1..Q4: Channel status display (green) for ports 1, 2, 3 and 4
- F1..F4: Port error display (red) for ports 1, 2, 3 and 4
- PWR: Supply voltage display (green)
•
Informative front-side module inscription
- Plain-text marking of the module type and function class
- 2D matrix code (article number and serial number)
- Connection diagram
- CM module class color coding: Silver
- Hardware and firmware version
- Complete Article No.
•
Optional accessories
- Labeling strips
- Reference identification label
- Color-coded label with color code CC04
•
Optional system-integrated shield connection
CM 4xIO-Link overview
Overview of BaseUnits
Communication module
Article number
CC code
BU type
P. unit
CM 4xIO-Link
6ES7137-6BD00-0BA0
CC04
A0
1
BaseUnit
Article number
CC codes for process terminals
CC codes for AUX terminals
P. unit
BU type A0
• New load group (light)
• 16 process terminals
• with 10 AUX terminals
6ES7193-6BP20-0DA0
CC01 to CC05
CC71 to CC73
1
BU type A0
• New load group (light)
• 16 process terminals
• with 10 AUX terminals
6ES7193-6BP20-2DA0
CC01 to CC05
CC71 to CC73
10
BU type A0
• New load group (light)
• 16 process terminals
• without AUX terminals
6ES7193-6BP00-0DA0
CC01 to CC05
--
1
BU type A0
• New load group (light)
• 16 process terminals
• without AUX terminals
6ES7193-6BP00-2DA0
CC01 to CC05
--
10
BU type A0
• Load group forwarding (dark)
• 16 process terminals
• with 10 AUX terminals
6ES7193-6BP20-0BA0
CC01 to CC05
CC71 to CC73
1
BU type A0
• Load group forwarding (dark)
• 16 process terminals
• with 10 AUX terminals
6ES7193-6BP20-2BA0
CC01 to CC05
CC71 to CC73
10
BU type A0
• Load group forwarding (dark)
• 16 process terminals
• without AUX terminals
6ES7193-6BP00-0BA0
CC01 to CC05
--
1
BU type A0
• Load group forwarding (dark)
• 16 process terminals
• without AUX terminals
6ES7193-6BP00-2BA0
CC01 to CC05
--
10
© Siemens AG 2016