SIEMENS
2/61
Siemens IC 10 · 2017
* You can order this quantity or a multiple thereof.
Illustrations are approximate
AS-Interface
Slaves
I/O Modules for Use in the Field, High Degree of Protection
Digital I/O modules IP68/IP69K - K60R
2
IP68/IP69K tests
K60R modules were tested with the following tests:
•
Stricter test than IP67: 90 min at 1.8 m depth of water
(IP67: 30 min at 1 m depth of water)
•
Salt water test: Five months in salt water, 20 cm deep, at room
temperature
•
Test with particularly creepable oil: Five months completely
under oil at room temperature
•
Test with drilling emulsion: Five months at room temperature
(components of the drilling emulsion: Anionic and non-ionic
emulsifiers, paraffinic low-aromatic mineral oil, boric acid
alkanolamines, corrosion inhibitors, oil content 40 %)
•
Test in oil bath (Excellence 416 oil) with alternating oil bath
temperature: 130 cycles of 15 to 55 °C, two months
•
Cleaning with a high-pressure cleaner according to IP69K:
80 to 100 bar, 10 to 15 cm distance, time per side > 30 s,
water temperature 80 °C
To simulate requirements as realistically as possible,
the modules were artificially aged prior to the tests by
15 temperature cycles of -25/+85 °C. During the test, the
modules were connected to 3RX1 connecting cables.
Unassigned connections were closed with 3RK1901-1KA00
sealing caps.
Note:
Sealing caps and M12 connections must be tightened with the
correct torque.
■
Selection and ordering data
Version
SD
Article No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
d
3RK1400-1CR00-0AA3
Digital I/O modules IP68/IP69K - K60R
• 4 inputs / 4 outputs
• Width 60 mm
• IP68/IP69K
• Standard assignment
• Current carrying capacity
-
200 mA (inputs)
-
2 A (outputs)
• Standard slave
• Modules supplied without mounting plate
2
3RK1400-1CR00-0AA3
1
1 unit
42C
© Siemens AG 2016