SIEMENS
7/112
Siemens IK PI · 2015
Industrial Remote Communication
SIMATIC Teleservice
TeleService
7
TS Adapter IE Advanced
Functionality:
•
Remote maintenance via a VPN connection
•
Parameterization via an integrated web interface
•
Enabling and disabling of connections, time-triggered if
required
•
User management with freely-definable password rules
•
Logging of security events, exportable
•
Own hardware clock, battery back-up, NTP client
•
Configurable package filter
•
Port forwarding routing
•
NAT, SNMP
•
Sending e-mails (via FBs on a SIMATIC CPU)
•
Export and import of parameters
•
Firmware update
Security:
The TS Adapter IE Advanced provides a high level of security,
supported by hardware. System access is only possible via an
encrypted VPN connection. Authentification is ensured by
certificates.
The user management function enables user accounts with
differing access rights to be set up. The firewall can be config-
ured to filter data streams so they exactly fit customer require-
ments.
Advantages/customer benefits:
•
High security standard due to VPN, certificates, hardware-
generated random numbers and adherence to strict Siemens
security guidelines
•
Made-to-measure solutions for remote maintenance in the
automation environment
•
Transparent routing via web proxies ensures use directly from
the company LAN (service side) to the system, with no release
or configuration by IT administrators
•
Only the TIA Portal is required to build up the VPN connection
(VPN client)
- SSTP (Windows 7 service) behaves like HTTPS access from
the browser and is thus transparent in the infrastructure
- Direct online connection from the TIA Portal at the press of a
button (telephone book function: management of
multiple teleservice adapters possible)
•
Can be used as router or following a default router
•
Integrated DCP proxy (support for life-list function as local,
and use of topology editor via remote access)
Sending e-mails
The TS Adapter IE Advanced (gateway function) can be used to
send e-mails from a SIMATIC-CPU in the system network (LAN)
to a communication partner in the public grid (WAN).
The following blocks are available depending on the CPU used:
•
TMAIL_C for S7-1500
•
TM_MAIL for S7-1200 (for firmware versions V2.x and V3.x of
a CPU from the S7-1200 series)
•
AS_MAIL for S7-300/400
■
Technical specifications
TS Adapter II
Dimensions (W x H x D) in mm
125 x 110 x 40
Weight, approx.
250 g
Interfaces
• to S7/C7
RS 485 (up to 12 Mbit/s)
• to the PC
USB 1.1 (12 Mbit/s)
• to an external modem
RS 232 (up to 115 kbaud)
• to the analog telephone network
RJ12
• to the ISDN telephone network
RJ45
Supply voltage,
external or via MPI interface
24 V DC
Current consumption
60 mA (typ.) / 120 mA (max.)
Switch-on current, max.
0.7 A; 8 μs
Degree of protection
IP20
Temperature
• Operation
± 0 °C to +60 °C
• Storage/transport
-40 °C to +70 °C
TS Adapter IE
Dimensions (W x H x D) in mm
125 x 110 x 40
Weight, approx.
approx. 370 g
Interfaces
• Ethernet
RJ45 (10/100 Mbit/s)
• to an external modem
RS 232 (up to 115 kbaud)
• to the analog telephone network
RJ12
• to the ISDN telephone network
RJ45
Supply voltage,
external or via MPI interface
24 V DC
Current consumption
of the TSA-IE ISDN
typ. 170 mA / max. 230 mA
Current consumption
of the modem TSA IE
typ. 180 mA / max. 240 mA
Switch-on current, max.
0.7 A; 8 μs
Degree of protection
IP20
Temperature
• Operation
± 0 °C to +60 °C
• Storage/transport
-40 °C to +70 °C
© Siemens AG 2014