SIEMENS
7/108
Siemens IK PI · 2015
■
Overview
(continued)
Industrial Remote Communication
SIMATIC Teleservice
TeleService
7
•
Additional functions with TS Adapter IE:
- Remote operation of HMI devices:
Access to the HMI device via an Internet browser installed
on the adapter
- Sending e-mails:
Establishing a modem link to a dial-up server (e.g. to an
Internet service provider): A SIMATIC CPU can send e-mails
over an e-mail server that can be accessed in this manner.
- Standard routing:
A modem link can be established to an Internet service
provider for accessing data on the Internet.
•
Additional functions with TS Adapter IE Advanced:
- Remote connection via the Internet
■
Application
With TeleService, remote servicing of SIMATIC S7 automation
systems or HMI devices is possible using the programming
device or PC over a fixed line/wireless network or via the Internet
(TS Adapter IE Advanced). With the help of TeleService, the
connection to the automation components is extended over the
telephone network to the programming device or PC. The func-
tions to be performed, such as programming, are completed
using the same tools and functionality as if the job was being
done locally.
The user has access to the familiar functions
of STEP 7 and the engineering tools, comparable to a local con-
nection.
TeleService increases the effective availability of plants and
machines. Access through TeleService means that technical
services (e.g. maintenance, updating, and troubleshooting) can
be performed cost-effectively from a central service center.
Apart from teleservice, a remote link to a programming device
or PC can be established program-controlled using a function
block call. This link allows process data to be exchanged
between an S7 CPU and the programming device or PC with
support from PRODAVE.
■
Design
Different components are required depending on the
TeleService function or TS Adapter.
For remote maintenance:
•
TeleService engineering software
(not required when using the TIA Portal)
•
A programming device/PC-side modem
(TS Adapter II, TS Adapter IE or TS Adapter IE Basic)
•
Internet access on the programming device/PC side
(TS Adapter IE Advanced)
•
A TS Adapter, line-side
Required in addition to the components for remote maintenance
in the case of PG/PLC remote coupling:
•
PRODAVE V5.0 and higher for PG/PC:
Toolbox for process data traffic between SIMATIC S7/C7 and
the PC for autonomous processing of data traffic
•
"PG_DIAL" function block (included in TeleService software
package) for the PLC
•
A TS Adapter II, line-side
Required in addition to the components for remote maintenance
in the case of PLC/PLC remote coupling:
•
TS Adapter for the second PLC
•
"AS_DIAL" function block (included in TeleService software
package) for the PLCs
•
A TS Adapter II, line-side
For sending SMSes:
•
Engineering Software TeleService Version 5.2 and higher
•
GSM wireless modem on line side, Hayes-compatible
•
TS Adapter II, line-side
•
Modem cable for connecting the TS Adapter and modem
(included in TS Adapter II package)
For sending e-mails:
•
Engineering Software TeleService Version 6.1 and
higher or TIA portal
•
TS Adapter IE, TS Adapter IE Basic or TS Adapter IE
Advanced, line-side
•
Internet service provider and an e-mail server that can be
accessed there
For remote control of HMI devices:
•
PG/PC with browser – e.g. Internet Explorer – and the
Sm@rtViewer
•
TS Adapter IE, TS Adapter IE Basic or TS Adapter IE
Advanced, line-side
•
SIMATIC HMI device with an installed Runtime option of
WinCC flexible /Sm@rtService or /Sm@rtAccess.
For further information on WinCC flexible and the Sm@rt
options, see
© Siemens AG 2014