SIEMENS
7/79
Siemens IK PI · 2015
Industrial Remote Communication
TeleControl Professional
Stations for ST7 protocol
TIM 4R-IE for WAN and Ethernet
7
■
Technical specifications
Article No.
6NH7800-4BA00
Product-type designation
TIM 4R-IE
Transmission rate
Transfer rate
• for Industrial Ethernet
10 … 100 Mbit/s
• in accordance with RS 232
50 … 38 400 bit/s
Interfaces
Number of interfaces according to
Industrial Ethernet
2
Number of electrical connections
• for external data transmission
in accordance with RS 232
2
• for power supply
1
Design of electrical connection
• the Industrial Ethernet Interface
RJ45 port
• at interface 1
for external data transmission
9-pin D-sub connector,
RS232 switchable to RS485
• at interface 2
for external data transmission
9-pin D-sub connector,
RS232 switchable to RS485
• for power supply
2-pin, pluggable terminal strip
design of the removable storage
C-PLUG
Yes
Supply voltage, current consump-
tion, power loss
Type of supply voltage
DC
Supply voltage
24 V
• minimum
20.4 V
• maximum
28.8 V
Consumed current
• from backplane bus at 24 V
for DC maximum
0.2 A
• from external supply voltage
at 24 V with DC maximum
0.17 A
Resistive loss
4.6 W
Product expansion optional
backup battery
Yes
Type of battery
Lithium AA / 3.6 V / 2.3 Ah
Backup current
• typical
100 μA
• maximum
160 μA
Permitted ambient conditions
Ambient temperature
• during operating
0 … 60 °C
• during storage
-40 … +70 °C
• during transport
-40 … +70 °C
Relative humidity at 25 °C without
condensation during operating
maximum
95 %
Protection class IP
IP20
Design, dimensions and weight
Module format
Compact module S7-300
double width
Width
80 mm
Height
125 mm
Depth
120 mm
Net weight
0.4 kg
Product properties, functions,
components
general
Number of modules note
Number of TIM 4R-IE per
S7-300/S7-400: multiple,
number depends on the connection
resources of the CPU
Cable length
• with RS 232 interface maximum
6 m
• with RS 485 interface maximum
30 m
Performance data
Performance data
S7 communication
Number of possible connections
for S7 communication
• maximum
64
• with PG connections maximum
2
• with OP connections maximum
62
• note
-
Service
• SINAUT ST7
through S7 communication
Yes
• PG-/OP-communication
Yes
Performance data
multi-protocol mode
Number of active connections with
multiprotocol mode
128
Performance data
telecontrol
Suitability for use
• node station
Yes
• substation
Yes
• control center
Yes
• note
-
Protocol is supported
Yes
• TCP/IP
• DNP3
No
• SINAUT ST1 protocol
Yes
• SINAUT ST7 protocol
Yes
Product function data buffering
if connection is aborted
Yes
• note
56 000 data messages
Storage capacity
• of user memory of S7 CPU
-
for TD7onCPU mode data blocks
on CPU required
20 Kibyte
-
for TD7onTIM mode data blocks
on TIM required
0 Kibyte
• note
TD7onCPU:
at least 20 KB, actual requirement
determined by data volume and
functional scope
TD7onTIM:
0 bytes in most favorable case
Product property retentive message
frame memory
Yes
Transmission format
• for SINAUT ST1 protocol
with polling 11 bit
Yes
• for SINAUT ST1 protocol
with spontaneous 10 bit or 11 bit
Yes
• for SINAUT ST7 protocol
with multi-master polling 10 bit
Yes
•
for SINAUT ST7 protocol with polling
or spontaneous 10 bit or 11 bit
Yes
Article No.
6NH7800-4BA00
Product-type designation
TIM 4R-IE
© Siemens AG 2014