Industrial Remote Communication
TeleControl Professional for the control center
WinCC/TeleControl
Outstations/remote terminal units
WinCC/TeleControl for WinCC V7.0 SP2 supports the following
preferred outstations for local distributed automation:
•
Controller integrated into ET 200S (IEC 870-5-101/104
telecontrol protocols); for cost-sensitive applications, up to
approx. 30 I/O signals or approx. 200 data points
•
S7-300/S7-300F controller (SINAUT ST7, DNP3, IEC 870-5-
101/104 telecontrol protocols); for extremely flexible configu-
ration, up to 100 I/O signals or approx. 2 000 data points
•
S7-400/S7-400F controller (SINAUT ST7, DNP3, IEC 870-5-
101/104 telecontrol protocols); up to 500 I/O signals or
approx. 5 000 data points
•
S7-400/S7-400F redundant controller (IEC 870-5-101/104 and
DNP3 telecontrol protocols); up to 500 I/O signals or approx.
5 000 data points
•
Third-party station with the IEC 870-5-101/104 and DNP3
telecontrol protocols (depending on type of station)
The following table provides an overview of the current options for connecting to these outstations:
1)
Data buffering is limited to two SIMATIC S7 data blocks. Depending on the SIMATIC CPU,
this corresponds to approx. 800 to 3200 buffered frames.
Spectrum of outstations and integration versions
Telecontrol protocol
SINAUT ST 7
DNP3
IEC 870-5-01
IEC 870-5-04
Type of communication
Serial
Ethernet TCP/IP
Serial
Ethernet TCP/IP
Serial
Ethernet TCP/IP
Interface
TIM 4R-IE
TCP/IP WAN router
or/and TIM 4R-IE
TCP/IP serial
converter
TCP/IP WAN
router
TCP/IP serial
converter
TCP/IP WAN router
RTU/interface
ET 200S with
integr. CPU
(corresponding
to S7-314)
-
-
-
-
IM 151-7 CPU or
IM 151-8 PN/
DP CPU
as well as
1 SI module +
SIPLUS RIC library
IM 151-8 PN/
DP CPU
+ SIPLUS RIC
library
S7-300/S7-300F
TIM 3V-IE
TIM 3V-IE
TIM 3V-IE DNP3
TIM 3V-IE DNP3
CP 341
+ SIPLUS RIC
library
CP 343 + IEC on S7
or integr. PN
interface
+ SIPLUS RIC
library
S7-400/S7-400F
TIM 4R-IE
TIM 4R-IE
TIM 4R-IE DNP3
TIM 4R-IE DNP3
CP 441
+ SIPLUS RIC
library
CP 443 + SIPLUS
RIC library or integr.
PN interface
+ SIPLUS RIC
library
S7-400H/
S7-400FH
-
-
TIM 4R-IE DNP3
TIM 4R-IE DNP3
ET 200M +
2 x CP 341 +
SIPLUS RIC library
CP 443
+ SIPLUS RIC
library
Third-party station
-
-
Depends on type of station
Depends on type of station
Dial-up lines
•
-
•
-
-
-
Dedicated line and radio networks
•
•
•
•
•
•
Master/slave
•
•
•
•
•
•
Peer-to-peer
•
•
-
-
•
•
Mesh networks
•
•
•
•
•
•
Time tagging in RTU
•
•
•
•
•
•
RTU time synchronization
•
•
•
•
•
•
Data buffering in RTU
•
•
•
•
•
1)
•
1)
Routing with SIMATIC PDM
•
•
-
-
-
•
International standard
-
-
•
•
•
•
© Siemens AG 2014