SIEMENS
6/183
Siemens IK PI · 2015
6
■
Technical specifications
(continued)
Industrial Wireless Communication
WirelessHART
IE/WSN-PA LINK
Standards, specifications,
approvals
Standard for WirelessHART
HART V 7.1
HART V 7.1
Standard for wireless communication
IEEE 802.15.4
Yes
Yes
Verification of suitability
• CE mark
Yes
Yes
• concerning CSA
CSA Division 2 & Dust Ignition-proof for Class I, Division 2,
Groups A, B, C, and D. Dust Ignition-proof for Class II,
Groups E, F, and G / Suitable for Class III Hazardous
Locations. / Install per Siemens drawing A5E02467236A.
Temperature Code: T4 (-40°C < Ta < 60°C) CSA Enclosure
Type 4X
CSA Division 2 & Dust Ignition-proof for Class I, Division 2,
Groups A, B, C, and D. Dust Ignition-proof for Class II,
Groups E, F, and G / Suitable for Class III Hazardous
Locations. / Install per Siemens drawing A5E02467236A.
Temperature Code: T4 (-40°C < Ta < 60°C) CSA Enclosure
Type 4X
• concerning FM
FM Division 2, Non-Incendive for Class I, Division 2, Groups
A, B, C, and D. Dust Ignition-proof for Class II, III, Division
1, Groups E, F, and G / Indoor and outdoor locations /
NEMA Type 4X Temperature Code: T4 (-40°C < Ta < 60°C)
FM Division 2, Non-Incendive for Class I, Division 2, Groups
A, B, C, and D. Dust Ignition-proof for Class II, III, Division
1, Groups E, F, and G / Indoor and outdoor locations /
NEMA Type 4X Temperature Code: T4 (-40°C < Ta < 60°C)
• concerning ATEX
ATEX type n, see note: certificate number:
Baseefa10ATEX0044X, ATEX marking: Ex II 3 G,
Ex nA nL IIC T4 (-40°C <= Ta <= 60°C), rated voltage: 28 V,
ATEX dust ignition-proof: certificate number:
Baseefa10ATEX0045X, ATEX marking:
II 3D, Ex tD A22 IP66 T135 (-40°C <= Ta <= 60°C),
rated voltage: 28 V. Note on type n: conditions for safe
handling during installation. The device does not pass the
500 V insulation test in accordance with paragraph 6.8.1 of
EN 60079-15:2005. This must be taken into account when
the device is mounted
ATEX type n, see note: certificate number:
Baseefa10ATEX0044X, ATEX marking: Ex II 3 G,
Ex nA nL IIC T4 (-40°C <= Ta <= 60°C), rated voltage: 28 V,
ATEX dust ignition-proof: certificate number:
Baseefa10ATEX0045X, ATEX marking:
II 3D, Ex tD A22 IP66 T135 (-40°C <= Ta <= 60°C),
rated voltage: 28 V. Note on type n: conditions for safe
handling during installation. The device does not pass the
500 V insulation test in accordance with paragraph 6.8.1 of
EN 60079-15:2005. This must be taken into account when
the device is mounted.
• regarding IECEx
IECEx type n, see note: certificate number:
IECEx BAS 10.0014X, Ex nA nL IIC T4 (-40°C <= Ta <=
60°C), rated voltage: 28 V, IECEx dust ignition-proof,
see note: certificate number: IECEx BAS 10.0015X,
Ex tD A22 IP66 T135 (-40°C <= Ta <= 60°C),
rated voltage: 28 V. Note on type n: conditions for safe
handling during installation. The device does not pass the
500 V insulation test in accordance with paragraph 6.8.1 of
EN 60079-15:2005. This must be taken into account when
the device is mounted.
IECEx type n, see note: certificate number:
IECEx BAS 10.0014X, Ex nA nL IIC T4 (-40°C <= Ta <=
60°C), rated voltage: 28 V, IECEx dust ignition-proof,
see note: certificate number: IECEx BAS 10.0015X,
Ex tD A22 IP66 T135 (-40°C <= Ta <= 60°C),
rated voltage: 28 V. Note on type n: conditions for safe
handling during installation. The device does not pass the
500 V insulation test in accordance with paragraph 6.8.1 of
EN 60079-15:2005. This must be taken into account when
the device is mounted.
• regarding NEMA
-
-
Wireless approval
FCC and IC approval
IC approval
Article No.
6GK1411-6CA40-0AA0
6GK1411-6CA40-0BA0
Product-type designation
IE/WSN-PA LINK
IE/WSN-PA LINK
© Siemens AG 2014