SIEMENS
6/177
Siemens IK PI · 2015
■
Technical specifications
(continued)
Industrial Wireless Communication
WirelessHART
SITRANS AW210 WirelessHART adapter
6
Explosion protection
Intrinsic safe "i" gases and vapors
II 1G Ex ia IIC T*; IP68
T* = T5 for Ta = -40 ... +85 °C
T* = T6 for Ta = -40 ... +75 °C
Intrinsic safe dust
II 1 D Ex iaD 20 IP68 T95C;
Ta = -40 ... +85 °C
Non-sparking (zone 2)
II 3 G Ex nA nC IIC T* Gc; IP68
T* = T5 for Ta = -40 ... +85 °C
T* = T6 for Ta = -40 ... +75 °C
Explosion protection to FM for US
Intrinsic safe, Non-sparking
IS/I,II,III/1/ABCDEFG/
T5 Ta = -40 ... +85 °C,
T6 Ta = -40 ... +75 °C
NI/I/2/ABCD/
T5 Ta = -40 ... +85 °C,
T6 Ta = -40 ... +75 °C
S/II,III/2/EFG/
T5 Ta = -40 ... +85 °C,
T6 Ta = -40 ... +75 °C
I/0/AEx ia/IIC/
T5 Ta = -40 ... +85 °C
T6 Ta = -40 ... +75 °C;
20/AEx iaD/T95°C;
Ta = -40 ... 85°C
I/2/AEx nA nC/IIC/
T5 Ta = -40 ... +85 °C,
T6 Ta = -40 ... +75 °C; IP68
Explosion protection to FM for CA
Intrinsic safe, Non-sparking
IS/I,II,III/1/ABCDEFG/
T5 Ta = -40 ... +85 °C
T6 Ta = -40 ... +75 °C;
NI/I/2/ABCD/
T5 Ta = -40 ... +85 °C
T6 Ta = -40 ... +75 °C;
S/II,III/2/EFG/
T5 Ta = -40 ... +85 °C
T6 Ta = -40 ... +75 °C;
I/0/Ex ia/IIC/
T5 Ta = -40 ... +85 °C
T6 Ta = -40 ... +75 °C;
I/2/Ex nA nC/IIC/
T5 Ta = -40 ... +85 °C
T6 Ta = -40 ... +75 °C
II/1/EFG Ta = -40 ... +85°C; IP68
Flameproof gases and vapors
II 2 G Ex d IIC T* Gb; IP68
T* = T5 for Ta = -40 ... +85 °C
T* = T6 for Ta = -40 ... +75 °C
Protection by enclosure dust
II 2 D Ex tb IIIC T95°C
Ta = -40 ... +85°C; IP68
Explosion protection to FM for US
Explosionproof, flameproof, gas, dust
XP/I/1/ABCD
I/1 AEx d IIC T5, T6 Gb
DIP/II,III/1/EFG
21/AEx tb IIIC T95°C
T5 Ta = -40 ... +85°C,
T6 Ta = -40 ... +75°C
Type 6P, IP68
Explosion protection to FM for CA
Explosionproof, flameproof, gas, dust
XP/I/1/ABCD
I/1 Ex d IIC T5, T6 Gb
DIP/II,III/1/EFG
T5 Ta = -40 ... +85°C,
T6 Ta = -40 ... +75°C
■
Ordering data
Article No.
Note:
Circuit diagrams and dimensional drawings can be found in
Catalog FI 01.
Configuration
SITRANS AW210
Adapter for WirelessHART
Communication
7MP3111
-
7 7
7 7
0
-
0
A
A
0
WirelessHART-Adapter AW210
with 4 ... 20 mA-
or HART-interface
• 2 devices
1
• 8 devices
2
Auxiliary power
Loop powered or 24 VDC (external)
A
Certificates and approvals
Intrinsically safe gas, vapors and
dust (ATEX), Intrinsic Safe (FM)
B
Explosionproof gas, vapour and
dust (ATEX), Explosionproof (FM)
C
Enclosure
Aluminum
0
© Siemens AG 2014