SIEMENS
6/172
Siemens IK PI · 2015
■
Function
(continued)
Industrial Wireless Communication
WirelessHART
SITRANS AW200 WirelessHART adapter
6
Terminal block with 6 screw connection clamps
Parameterization
SITRANS AW200 configured via HART. Configuration can be
carried out using a handheld communicator or, more conve-
niently, with a HART modem and the SIMATIC PDM configuration
software.
Initial startup of the adapter is usually carried out via
SIMATIC PDM and a HART modem or a handheld communica-
tor. During initial startup, the network ID and join key are set in
the adapter. These parameters are used to integrate the adapter
into an existing WirelessHART network.
Following integration into the network, the adapter and
HART devices connected can be conveniently operated via
the WirelessHART network or with the local HART modem.
Siemens HART field devices for the adapter
HART and 4…20mA field devices can be connected to the
SITRANS AW200 WirelessHART adapter. Depending on the
electrical data of the field devices, they can receive their
power supply from the WirelessHART adapter or will require
an external power supply.
See
for
FAQ with the latest information on connectivity for Siemens field
devices.
Note:
Siemens has only approved the Siemens HART field devices
listed there for the adapter, and will only provide technical sup-
port for these devices.
Based on HART specifications, it is generally possible to con-
nect devices that are not listed, however with the following limi-
tations:
•
All warranties and liability will be excluded
•
No technical support
Interface
Connection
Function
1
Power supply for the field device
2
HART/4 ... 20 mA
3
External supply/Dimensions
4
High-resistance HART connection
5, 7
High-resistance HART connection
6, 8
Mass, high-resistance connection
■
Technical specifications
Input
Input
Point-to-Point connection to a HART
field device or
Point-to-Point connection to a
4 ... 20 mA field device or
up to four HART field devices with
external power supply which are inte-
grated using the multidrop method
Communication
HART communication using
multidrop method, 4 ... 20 mA power
signal with Point-to-Point connection
Protocol
HART V7 (compatible with previous
HART versions)
Transfer rate
1200 bits/s using HART multidrop
method
Output
Communication
WirelessHART V7
Transfer rate
Nominal 250 kBits/s
Transmission frequency band
2.4 GHZ (ISM band)
Range (under reference conditions)
Outside areas up to 250 m,
within buildings up to 50 m
RF signal strength
Can be configured:
0 dBm and 10 dBm
Output signals
• WirelessHART Adapter
Measured voltage and up to three
other variables may be selected from
the following: adapter temperature,
battery voltage, energy consumed,
expected battery service life
• 4 ... 20 mA field device
Scaled or linearized process values
• HART field device
up to four process variables, can be
configured via PDM or gateway
Measuring accuracy
(as per reference conditions
IEC 61298-2)
Max. measuring error
(4 ... 20 mA circuit)
0.125 % re: measuring range
Effect of ambient temperature
(4 ... 20 mA circuit)
5 μA/0°K
Rated conditions
Location
Outside/Inside
Ambient conditions
• Ambient temperature
-40 ... +80 °C (-40 ... +176 °F)
The capacity of the battery
decreases rapidly if ambient
temperature falls flow -30 °C.
• Storage temperature
-40 ... +85 °C (-40 ... +185 °F)
without batteries
< 21 °C with batteries
• Relative humidity
Max 90 % at 25 °C (non-condensat-
ing)
• Resistance to vibration
20
f
2000 Hz: 0.01 g²/Hz as per
IEC 68-2-64
• Shock resistance
15 g, 11 ms as per IEC 68-2-27
Electromagnetic compatibility
As per EN 61326, EN 301 489-1/17
and NAMUR NE 21