General data
3
■
More information
(continued)
Protective separation
All circuits in SIMOCODE pro are safely isolated from each other
in accordance with IEC 60947-1. That is, they are designed with
double creepages and clearances. In the event of a fault, there-
fore, no parasitic voltages can be formed in neighboring circuits.
The instructions of Test log No. 2668 must be complied with.
Types of protection EEx e and EEx d
The overload protection and the thermistor motor protection
of the SIMOCODE pro system comply with the requirements for
overload protection of explosion-proof motors to the type of
protection:
•
EEx d "flameproof enclosure" e.g. according to IEC 60079-1
•
EEx e "increased safety" e.g. according to IEC 60079-7
When using SIMOCODE pro devices with a 24 V DC control
voltage, electrical separation must be ensured using a battery or
a safety transformer according to IEC 61558-2-6. EC type test
certificate: BVS 06 ATEX F 001
Test log: BVS PP 05.2029 EG.
Selection data for type-tested
assemblies/load feeders
For configuration tables according to type of coordination "1"
or "2", see
•
Manual "Configuring SIRIUS",
Article No.: 3ZX1012-0RA21-0AB0,
•
Manual "Configuring SIRIUS Innovations",
Article No.: 3ZX1012-0RA21-1AB0,
•
SIMOCODE pro PROFIBUS System Manual,
Article No.: 3UF7970-0AA01-0,
•
SIMOCODE pro PROFINET System Manual,
Article No.: 3ZX1012-0UF70-1AB1,
System manual
The SIMOCODE pro system manual describes the motor
management system and its functions in detail. It provides
information on configuration, start-up, servicing and mainte-
nance. A typical example of a reversing starter application is
used to teach the user quickly and practically how to use the
system. In addition to help on how to identify and rectify faults
in the event of a malfunction, the manual also contains special
information for servicing and maintenance. For selection of
equipment and for planning, it is recommended to consult the
system manual.
A detailed description of the DM-F Local and DM-F PROFIsafe
fail-safe expansion modules is provided in the system manual
"SIMOCODE pro Safety Fail-Safe Digital Modules", which can be
downloaded from the Internet.
Internet
More information see
www.siemens.com/simocode
.
© Siemens AG 2014