SIEMENS
4/104
Siemens IK PI · 2015
AS-Interface
Slaves
Motor starters for use in the field, high degree of protection
SIRIUS M200D motor starters
> M200D motor starters for AS-Interface
4
■
Overview
(continued)
✓
Function available
--
Function not available
■
Application
The M200D AS-i standard is particularly suitable for highly
automated applications in conveyor systems, which require that
devices and systems be monitored to prevent or limit plant
downtime. The option of planning the functions of the motor
starter or its interfaces also makes fine-adjustment to the
function of the motor starter in the application possible and
hence provides for extreme flexibility.
SIRIUS M200D
SIRIUS M200D
AS-i Basic
AS-i Standard
Device functions (firmware features)
Device function
Repair switch
✓
Lower current limit monitoring
--
✓
Parameterizable
Upper current limit monitoring
--
✓
Parameterizable
Zero current detection
✓
Permanent function: disconnection, less than
18.75% of the rated operational current
I
e
✓
Parameterizable
Blocking current
✓
Permanent function:
starting up of the motor: tripping limit up to
800% of the rated operational current
I
e
for 10 s
Active operation:
Threshold for tripping "blocking current" up to
400% of the rated operational current
I
e
✓
Parameterizable
Unbalance
✓
Permanent function: up to 30 % of the rated
operational current
I
e
(only mechanical MS)
✓
Parameterizable
Load type
✓
Permanent function: 3-phase
✓
Parameterizable: 1 and 3-phase
Tripping class
✓
Parameterizable using DIP switches:
CLASS 10/deactivated
Parameterizable using Motor Starter ES,
data record: CLASS 5, 10, 15, 20
Protection against voltage failure
✓
✓
Parameterizable: activated/deactivated
Soft starter control function
Soft start function
--
✓
Only solid-state version
Bypass function
--
✓
Only solid-state version
© Siemens AG 2014