SIEMENS
4/73
Siemens IK PI · 2015
AS-Interface
Slaves
Special integrated solutions
AS-interface communication modules
4
■
Overview
(continued)
3RK1400-1CD00-0AA2, 3RK2400-1FD00-0AA2
AS-Interface communication modules
for printed circuit board installation
With the 4I/4O or 4I/3O module for printed circuit board installa-
tion, it is possible for up to four mechanical contacts or 3-con-
ductor sensors according to IEC 947-5-2 to be connected.
Up to four indicator lights via the 4I/4O module or up to three
indicator lights via the 4I/3O module can also be controlled.
The power for short-circuit proof solid-state switching outputs is
provided from an auxiliary voltage (24 V PELV).
Mounting is very easy using a "Card Edge Board-to-Board
Connector". This connector can be ordered for vertical and
horizontal mounting from the company AMP, for example:
•
180° version for vertical mounting (AMP):
Type 530843-2
•
90° version for horizontal mounting (AMP):
Type 650118-1
If the inputs are loaded with more than 200 mA, the module does
not respond to invoking by a master.
3RK1200-0CD00-0AA2
AS-Interface communication modules
for printed circuit board installation
With the 4I module for printed circuit board installation, it is
possible for up to four mechanical contacts or 3-conductor
sensors to be connected, the power for inputs being provided
from the AS-Interface cable.
Mounting is very easy using a "Card Edge Board-to-Board
Connector". This connector can be ordered for vertical and
horizontal mounting from the company AMP, for example:
•
180° version for vertical mounting (AMP):
Type 530843-2
•
90° version for horizontal mounting (AMP):
Type 650118-1
If the inputs are loaded with more than 200 mA, the module does
not respond to invoking by a master.
■
Selection and ordering data
Connection
Connection pad
AS-i +
27, 29
AS-i -
28, 30
Sensor+
17, 18, 23, 24
Sensor-
13, 14, 19, 20
IN1
21
IN2
22
IN3
15
IN4
16
U
aux
+ (L24+)
2, 4
U
aux
- (M24)
1, 3
OUT1
9
OUT2
10
OUT3
5
OUT4
6 (not assigned for 3RK2400-1FD00-0AA2 4I/3O module)
OUT-
7, 8
Not assigned
11, 12, 25, 26
Connection
Connection pad
AS-i +
27, 29
AS-i -
28, 30
Sensor+
17, 18, 23, 24
Sensor-
13, 14, 19, 20
IN1
21
IN2
22
IN3
15
IN4
16
Not assigned
1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 25, 26
Version
Slave type
Article No.
3RK1400-0CD00-0AA3
3RG9005-0SA00
4 inputs / 4 outputs
• Supply of I/Os using AS-Interface cable (max. 200 mA)
-
Printed circuit board with solder pins, protected by enclosure
Standard
3RK1400-0CD00-0AA3
• Supply of I/Os using external auxiliary voltage (24 V PELV)
-
Printed circuit board with solder pins, protected by enclosure
Standard
3RK1400-0CD01-0AA3
-
Printed circuit board with solder pins for horizontal mounting
Standard
3RG9005-0SA00
• Supply of outputs using external auxiliary voltage (24 V PELV)
-
Printed circuit board with gold-plated direct
connector for 30-pole male connector
socket for simple installation with direct connector
Standard
3RK1400-1CD00-0AA2
4 inputs / 3 outputs
• Supply of outputs using external auxiliary voltage (24 V PELV)
-
Printed circuit board with gold-plated direct
connector for 30-pole male connector
socket for simple installation with direct connector
A/B
3RK2400-1FD00-0AA2
4 inputs
• Printed circuit board with gold-plated direct connector
• For 30-pole male connector socket
• For simple installation with direct connector
Standard
3RK1200-0CD00-0AA2
© Siemens AG 2014