SIEMENS
3/115
Siemens IK PI · 2015
3
■
Technical specifications
(continued)
PROFIBUS
Optical networks with OLM
Plastic and PCF fiber-optic cable
Permitted ambient conditions
Ambient temperature
• during operating
-40 … +90 °C
-25 … +75 °C
-25 … +75 °C
• during storage
-40 … +90 °C
-30 … +75 °C
-30 … +75 °C
• during transport
-40 … +90 °C
-30 … +75 °C
-30 … +75 °C
• during installation
-5 … +50 °C
-5 … +50 °C
-5 … +50 °C
Ambient condition for (standard)
operation mode
-
-
-
Protection class IP
-
-
-
Burning behaviour
flame resistant according to
IEC 60332-1-2 and IEC 60332-3-22
(Cat. A)
flame-retardant
flame resistant according to
IEC 60332-1-2 and IEC 60332-3-22
(Cat. A)
Chemical resistance
• to mineral oil
Conditional resistance
resistant
Conditional resistance
• to grease
Conditional resistance
resistant
Conditional resistance
• to water
Conditional resistance
Conditional resistance
Conditional resistance
Radiological resistance to
UV radiation
resistant
resistant
resistant
Product properties, functions,
components
general
Product feature
• halogen-free
No
No
No
• silicon-free
Yes
Yes
Yes
Product component Rodent protection
No
No
No
Cable length for PCF FOC
• for Industrial Ethernet maximum
100 m
100 m
100 m
• for PROFIBUS maximum
400 m
400 m
400 m
Standards, specifications,
approvals
Verification of suitability
UL approval:
OFN (NEC Article 770, UL 1651) /
CSA approval: OFN 90 Cel, FT1, FT4
(CSA standard C22.2 No232-M1988)
-
UL approval:
OFN (NEC Article 770, UL 1651) /
CSA approval: OFN 90 Cel, FT1, FT4
(CSA standard C22.2 No232-M1988)
• RoHS conformity
Yes
Yes
Yes
Article No.
6XV1861-2A
6XV1861-2C
6XV1861-2D
Product-type designation
PCF Standard Cable GP
PCF Trailing Cable
PCF Trailing Cable GP
© Siemens AG 2014