SIEMENS
3/145
Siemens IK PI · 2015
■
Technical specifications
(continued)
PROFIBUS
Optical networks with OBT and integrated interface
Optical bus terminal OBT
3
Design, dimensions and weight
Design
compact
Width
50.5 mm
Height
138 mm
Depth
78 mm
Net weight
400 g
Mounting type
• 35 mm DIN rail mounting
Yes
• wall mounting
Yes
Standards, specifications,
approvals
Standard
• for EMC from FM
FM3611: Class 1, Divison 2, Group A,
B, C, D / T4, Class 1, Zone 2,
Group IIC, T4
• for hazardous zone
EN 60079-0: 2006,
EN60079-15: 2005, II 3 G Ex nA II
T4 KEMA 07 ATEX 0145X
• for safety of CSA and UL
UL 60950-1, CSA C22.2 Nr. 60950-1
• for hazardous area of CSA and UL
-
• for emitted interference
EN 61000-6-4 (Class A)
• for interference immunity
EN 61000-6-2
Verification of suitability
EN 61000-6-2, EN 61000-6-4
• CE mark
Yes
• C-Tick
Yes
Marine classification association
• American Bureau of Shipping
Europe Ltd. (ABS)
No
• Bureau Veritas (BV)
No
• Det Norske Veritas (DNV)
No
• Germanische Lloyd (GL)
No
• Lloyds Register of Shipping (LRS)
No
• Nippon Kaiji Kyokai (NK)
No
Article No.
6GK1500-3AA10
Product-type designation
PROFIBUS OBT
■
Ordering data
Article No.
PROFIBUS OBT
6GK1500-3AA10
Optical bus terminal for connecting
a PROFIBUS node or an RS485
segment without an integrated
optical interface to the optical
PROFIBUS; without a
Simplex connector
PROFIBUS plug-in cable 830-1T
For connecting a data terminal,
completely pre-assembled with
two sub-D connectors, 9-pin
• 1.5 m
6XV1830-1CH15
• 3 m
6XV1830-1CH30
SITOP compact 24 V/ 0.6 A
6EP1331-5BA00
1-phase power supply
with wide-range input
85 – 264 V AC/110 – 300 V DC,
stabilized output voltage 24 V,
rated output current value 0.6 A,
slim design
© Siemens AG 2014