SIEMENS
3/129
Siemens IK PI · 2015
3
■
Technical specifications
(continued)
PROFIBUS
Optical networks with OLM
OLM Optical Link Module
Permitted ambient conditions
Ambient temperature
• during operating
0 … 60 °C
0 … 60 °C
0 … 60 °C
• during storage
-40 … +70 °C
-40 … +70 °C
-40 … +70 °C
• during transport
-40 … +70 °C
-40 … +70 °C
-40 … +70 °C
Relative humidity at 25 °C
without condensation during
operating maximum
95 %
95 %
95 %
Protection class IP
IP40
IP40
IP40
Design, dimensions and weight
Design
compact
compact
compact
Width
39.5 mm
39.5 mm
39.5 mm
Height
112 mm
112 mm
112 mm
Depth
74.5 mm
74.5 mm
74.5 mm
Net weight
340 g
340 g
340 g
Mounting type
• 35 mm DIN rail mounting
Yes
Yes
Yes
• wall mounting
Yes
Yes
Yes
Product properties, functions,
components
general
Product function Ring redundancy
Yes
Yes
Yes
Standards, specifications,
approvals
Standard
• for EMC from FM
FM3611: Class 1, Divison 2, Group A,
B, C, D / T4, Class 1, Zone 2,
Group IIC, T4
FM3611: Class 1, Divison 2, Group A,
B, C, D / T4, Class 1, Zone 2,
Group IIC, T4
FM3611: Class 1, Divison 2, Group A,
B, C, D / T4, Class 1, Zone 2,
Group IIC, T4
• for hazardous zone
EN 60079-0: 2006, EN60079-15: 2005,
EN60079-28: 2007, II 3 (2) G Ex nA
[opis] IIC T4 KEMA 09 ATEX 0173X
EN 60079-0: 2006, EN60079-15: 2005,
EN60079-28: 2007, II 3 (2) G Ex nA
[opis] IIC T4 KEMA 09 ATEX 0173X
EN 60079-0: 2006, EN60079-15: 2005,
EN60079-28: 2007, II 3 (2) G Ex nA
[opis] IIC T4 KEMA 09 ATEX 0173X
• for safety of CSA and UL
UL 60950-1, CSA C22.2 Nr. 60950-1
UL 60950-1, CSA C22.2 Nr. 60950-1
UL 60950-1, CSA C22.2 Nr. 60950-1
• for hazardous area of CSA and UL
UL 1604 and UL 2279-15 (Hazardous
Location), CSA C22.2 No. 213-M1987,
Class 1 / Division 2 / Group A, B, C, D /
T4, Class 1 / Zone 2 / Group IIC / T4
UL 1604 and UL 2279-15 (Hazardous
Location), CSA C22.2 No. 213-M1987,
Class 1 / Division 2 / Group A, B, C, D /
T4, Class 1 / Zone 2 / Group IIC / T4
UL 1604 and UL 2279-15 (Hazardous
Location), CSA C22.2 No. 213-M1987,
Class 1 / Division 2 / Group A, B, C, D /
T4, Class 1 / Zone 2 / Group IIC / T4
• for emitted interference
EN 61000-6-4 (Class A)
EN 61000-6-4 (Class A)
EN 61000-6-4 (Class A)
• for interference immunity
EN 61000-6-2
EN 61000-6-2
EN 61000-6-2
Verification of suitability
EN 61000-6-2, EN 61000-6-4
EN 61000-6-2, EN 61000-6-4
EN 61000-6-2, EN 61000-6-4
• CE mark
Yes
Yes
Yes
• C-Tick
Yes
Yes
Yes
Marine classification association
• American Bureau of Shipping
Europe Ltd. (ABS)
Yes
Yes
Yes
• Bureau Veritas (BV)
Yes
Yes
Yes
• Det Norske Veritas (DNV)
Yes
Yes
Yes
• Germanische Lloyd (GL)
Yes
Yes
Yes
• Lloyds Register of Shipping (LRS)
Yes
Yes
Yes
• Nippon Kaiji Kyokai (NK)
Yes
Yes
Yes
Article No.
6GK1503-2CB00
6GK1503-3CB00
6GK1503-4CB00
Product-type designation
PROFIBUS OLM G11
PROFIBUS OLM G12
PROFIBUS OLM G22
© Siemens AG 2014